{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2340-5KP32-0CH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2340-5KP32-0CH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2340-5KP32-0CH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2340-5KP32-0CH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2340-5KP32-0CH0, molded case circuit breaker, 3-pole, 400 A rated continuous current, line protection, breaking capacity 187 kA at 240 V, ETU850 electronic trip unit.","salesMarkdown":"It carries a rated continuous current Iu of 400 A at 40 °C, with a breaking capacity of 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V — covering the full low-voltage range for industrial mains and feeder protection. The 110 mm depth fits standard enclosures with clearance for rear cable routing. Maximum power loss is 98.5 W. The undervoltage release (UVR) is factory-fitted as a supplied basic switch (3VA2340-5KP32-0AA0) with an integrated auxiliary trip (3VA9608-0BB24).","metaTitle":"Siemens 3VA2340-5KP32-0CH0 SENTRON MCCB, 400 A, 187 kA at 24","metaDescription":"Siemens SENTRON 3VA2340-5KP32-0CH0 molded case circuit breaker, 400 A rated continuous current, 187 kA breaking at 240 V. Active production. ETU850 trip unit. Available to order ag","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"400 A","at 45 °C":"400 A","at 50 °C":"400 A","at 55 °C":"375 A","at 60 °C":"350 A","at 65 °C":"325 A","at 70 °C":"300 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"Yes","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"98.5 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Rated continuous current Iu":"400 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2340-5KP32-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB24","Design of the overcurrent release":"ETU850","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"400 A","Adjustable response value current / li max.":"4 000 A","Adjustable response value current / li min.":"600 A","Adjustable response value current / lr min.":"160 A","Adjustable response value current / Isd max.":"4 000 A","Adjustable response value current / Isd min.":"240 A","Neutral conductors / upgradeable/retrofittable":"Yes","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"400 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"35 x 10","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c1b3b6c5f6d67465025ac41848ceb75e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=268792&mlfb=3VA2340-5KP32-0CH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2340-5KP32-0CH0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2340-5KP32-0CH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2340-5KP32-0CH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}