{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2340-6HL32-0BL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2340-6HL32-0BL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2340-6HL32-0BL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2340-6HL32-0BL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, molded case circuit breaker, order code 3VA2340-6HL32-0BL0, 400 A continuous rating, 3-pole, 242 kA breaking capacity at 240 V AC.","salesMarkdown":"It carries a 242 kA breaking capacity at 240 V AC, dropping to 187 kA at 415 V and 440 V, 121 kA at 500 V, and 7.5 kA at 690 V — the voltage-dependent interruption performance tells you exactly where this breaker can clear a fault without upstream coordination issues. The 400 A rating holds flat from 40 °C through 50 °C ambient, then derates to 385 A at 55 °C, 370 A at 60 °C, 355 A at 65 °C, and 340 A at 70 °C. ## Built-in auxiliary and release configuration The base switch variant is 3VA2340-6HL32-0AA0, so the -0BL0 suffix adds the UVR and the HQ alarm package on top of that core breaker. A trip indicator is present, giving a local mechanical flag when the breaker has tripped on fault. Dimensions are 248 mm high, 138 mm wide, and 110 mm deep — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures designed for SENTRON 3VA2 breakers.","metaTitle":"Siemens SENTRON 3VA2340-6HL32-0BL0 MCCB, 400 A, 3-Pole","metaDescription":"Siemens SENTRON 3VA2340-6HL32-0BL0 molded case circuit breaker, 400 A continuous, 3-pole, 242 kA at 240 V. Active production. Sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"4 000 A","Minimum":"600 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"7.5 kA","at 40 °C":"400 A","at 45 °C":"400 A","at 50 °C":"400 A","at 55 °C":"385 A","at 60 °C":"370 A","at 65 °C":"355 A","at 70 °C":"340 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"98.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2340-6HL32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"400 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB11","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c1b3b6c5f6d67465025ac41848ceb75e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=502808&mlfb=3VA2340-6HL32-0BL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2340-6HL32-0BL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2340-6HL32-0BL0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent industrial distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the breaking capacity of 3VA2340-6HL32-0BL0 at different voltages?","answer":"Breaking capacity is voltage-dependent: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 7.5 kA at 690 V. This covers most low-voltage distribution fault levels."},{"question":"Does 3VA2340-6HL32-0BL0 include an undervoltage release?","answer":"Yes, it ships with an undervoltage release (UVR) plus 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ type)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2340-6HL32-0BL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2340-6HL32-0BL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}