{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2340-6HN32-0BL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2340-6HN32-0BL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2340-6HN32-0BL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2340-6HN32-0BL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2340-6HN32-0BL0, molded case circuit breaker, 3-pole, 400 A continuous, 242 kA at 240 V, undervoltage release, 2 aux + 1 trip alarm + 1 electrical alarm switch, line protection.","salesMarkdown":"The Siemens SENTRON 3VA2340-6HN32-0BL0 is a 3-pole molded case circuit breaker (MCCB) rated for 400 A continuous at 40 °C, with a maximum breaking capacity of 242 kA at 240 V AC. At 415 V it still holds 187 kA, and at 690 V it drops to 7.5 kA, which is the voltage limit for this frame size. The 400 A continuous rating holds flat from 40 °C through 50 °C, then derates to 385 A at 55 °C, 370 A at 60 °C, 355 A at 65 °C, and 340 A at 70 °C — so if your panel ambient runs above 50 °C, you need to account for that thermal curve when sizing the load. This is a line-protection design, meaning it's configured for cable and busbar protection rather than motor or generator protection. That switch complement gives you status feedback for the breaker position and trip condition — useful for a BMS or PLC input without adding external relays. Physical footprint: 248 mm height, 138 mm width, 110 mm depth. That 110 mm depth is the overall body depth — it fits standard MCCB mounting plates and enclosure backpanels without needing a deep gland plate. The 138 mm width for a 3-pole frame is typical for this class; verify the busbar spacing and phase-to-phase clearance in your existing panel before committing the cutout. ## Operating environment Maximum power loss is 98.5 W — that's the heat the breaker dissipates at full rated current.","metaTitle":"Siemens 3VA2340-6HN32-0BL0 SENTRON MCCB, 400 A, 3-Pole, 242","metaDescription":"Siemens SENTRON 3VA2340-6HN32-0BL0 molded case circuit breaker, 400 A continuous, 3-pole, 242 kA at 240 V. Undervoltage release, auxiliary switches. Current lifecycle. Quoted to or","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"4 000 A","Minimum":"4 000 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"7.5 kA","at 40 °C":"400 A","at 45 °C":"400 A","at 50 °C":"400 A","at 55 °C":"385 A","at 60 °C":"370 A","at 65 °C":"355 A","at 70 °C":"340 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"98.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2340-6HN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"400 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB11","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c1b3b6c5f6d67465025ac41848ceb75e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=59266&mlfb=3VA2340-6HN32-0BL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2340-6HN32-0BL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2340-6HN32-0BL0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time."},{"question":"What is 3VA2340-6HN32-0BL0's listed depth?","answer":"The depth is 110 mm."},{"question":"What is 3VA2340-6HN32-0BL0's listed width?","answer":"The width is 138 mm."},{"question":"What compliance documentation does this brand provide for 3VA2340-6HN32-0BL0?","answer":"The evidence does not list specific compliance certifications (RoHS, REACH, UL, IEC) for this order code. Standard SENTRON 3VA documentation typically includes UL and IEC listings; verify the specific certs for your jurisdiction at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2340-6HN32-0BL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2340-6HN32-0BL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}