{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2340-6JQ32-0KL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2340-6JQ32-0KL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2340-6JQ32-0KL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2340-6JQ32-0KL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2340-6JQ32-0KL0, molded case circuit breaker, 3-pole, 400 A, interrupting capacity 242 kA at 240 V, line protection design, with communication function.","salesMarkdown":"Its interrupting capacity hits 242 kA at 240 V and 187 kA at 415 V and 440 V, so it handles high-fault utility feeds without cascading upstream. The 400 A rating holds flat from 40 °C through 50 °C, then derates to 375 A at 55 °C and 300 A at 70 °C — that thermal curve matters when you pack this into a warm enclosure. It ships with a shunt trip (STL) auxiliary release and a 2+1+1 auxiliary switch configuration (2 auxiliary switches, 1 trip alarm, 1 electrical alarm). The breaker measures 248 mm high by 138 mm wide by 110 mm deep. That 110 mm depth is the projection from the mounting surface — check your gland plate clearance if you're back-panel mounting in a shallow enclosure.","metaTitle":"Siemens 3VA2340-6JQ32-0KL0 SENTRON MCCB, 400 A, 242 kA at 24","metaDescription":"Siemens SENTRON 3VA2340-6JQ32-0KL0 molded case circuit breaker, 3-pole, 400 A, 242 kA at 240 V. Current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"4 000 A","Minimum":"600 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"7.5 kA","at 40 °C":"400 A","at 45 °C":"400 A","at 50 °C":"400 A","at 55 °C":"375 A","at 60 °C":"350 A","at 65 °C":"325 A","at 70 °C":"300 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Initial Value":"80 A","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Full-Scale Value":"400 A","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"96 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2340-6JQ32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Summation current formation L-conductor","Continuous Current / Rated Value":"400 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU560","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"Yes","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSIG","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c1b3b6c5f6d67465025ac41848ceb75e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=100274&mlfb=3VA2340-6JQ32-0KL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2340-6JQ32-0KL0/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source — 3VA2225-5JQ32-0AK0?","answer":"The 3VA2225-5JQ32-0AK0 is a smaller-frame SENTRON MCCB (225 A frame vs 400 A). It will not drop into the same panel cutout or bus connection without rewiring — the 3VA2340 frame is physically larger. If you need the 400 A rating and 242 kA interrupting capacity, this is the correct frame size."},{"question":"What is the depth of 3VA2340-6JQ32-0KL0?","answer":"The depth is 110 mm (4.33 in)."},{"question":"What is the width of 3VA2340-6JQ32-0KL0?","answer":"The width is 138 mm (5.43 in)."},{"question":"Where can I buy 3VA2340-6JQ32-0KL0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2340-6JQ32-0KL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2340-6JQ32-0KL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}