{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2440-5HN32-0AH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2440-5HN32-0AH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2440-5HN32-0AH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2440-5HN32-0AH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2440-5HN32-0AH0, molded case circuit breaker, 3-pole, 400 A rated current, 4800 A frame, line protection design.","salesMarkdown":"## What this MCCB carries The Siemens 3VA2440-5HN32-0AH0 is a SENTRON molded case circuit breaker sized for a 400 A continuous load on a 4800 A frame, 3-pole, designed for line protection in distribution panels. Rated current holds steady at 400 A across the full operating temperature range from 40 °C to 70 °C — no derating needed for warm enclosures or summer ambient conditions. Interrupting capacity varies by system voltage: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 9 kA at 690 V. That 187 kA at 240 V covers high-fault industrial services and transformer secondaries. Max power loss is 63.5 W — thermal dissipation to account for in enclosure sizing if the panel is tightly packed. ## Panel fit and integration Mounts on a DIN rail or bolts into a panel base. Dimensions: 248 mm high, 138 mm wide, 110 mm deep. The 138 mm width is the standard 3-pole MCCB footprint — fits existing SENTRON or third-party busbar systems without re-drilling. Comes with 2 auxiliary switches plus 1 trip alarm switch (HQ configuration) factory-fitted — no need to order separate signal contacts for status feedback to a PLC or remote annunciator. No undervoltage release, no ground-fault monitoring, no communication module on this variant. If those are needed, the 3VA family has other order codes with those options built in.","metaTitle":"Siemens 3VA2440-5HN32-0AH0 SENTRON MCCB, 400 A, 3-Pole, 4800","metaDescription":"Siemens 3VA2440-5HN32-0AH0 SENTRON molded case circuit breaker. 400 A continuous, 4800 A frame, 3-pole. Interrupting 187 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"4 800 A","Minimum":"4 800 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"9 kA","at 40 °C":"400 A","at 45 °C":"400 A","at 50 °C":"400 A","at 55 °C":"400 A","at 60 °C":"400 A","at 65 °C":"400 A","at 70 °C":"400 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Limited To 1 S":"5 kA","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"63.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2440-5HN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"Without auxiliary release","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"400 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"630 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0eb36652ce522f093395d6bd0dd27e34.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=85499&mlfb=3VA2440-5HN32-0AH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2440-5HN32-0AH0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2440-5HN32-0AH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2440-5HN32-0AH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}