{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2440-5HN32-0CL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2440-5HN32-0CL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2440-5HN32-0CL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2440-5HN32-0CL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2440-5HN32-0CL0, molded case circuit breaker, 3-pole, 400 A, ETU350 electronic trip unit, line protection, 110 x 138 x 248 mm.","salesMarkdown":"Breaking capacity is 187 kA at 240 V, dropping to 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V — the 415 V figure governs most European industrial distribution panels; the 690 V rating is the limiting case for 690 V line-ups. Temperature derating is minimal up to 50 °C (full 400 A), then drops to 384 A at 55 °C, 376 A at 60 °C, 368 A at 65 °C, and 360 A at 70 °C — the 55 °C step is where you lose headroom; plan the enclosure ventilation if ambient exceeds 50 °C. Dimensions are 110 mm deep, 138 mm wide, 248 mm tall — the 138 mm width is standard for 400 A frame MCCBs on DIN-rail or backplate mounting; verify the gland plate cutout against the existing panel layout if retrofitting into a tight enclosure. The ETU350 trip unit is a fixed-configuration electronic release; there is no communication module or phase-failure detection on this variant — the basic switch base is 3VA2440-5HN32-0AA0, and the integrated auxiliary trip is 3VA9608-0BB24.","metaTitle":"Siemens SENTRON 3VA2440-5HN32-0CL0 MCCB, 400 A, 3-Pole, ETU3","metaDescription":"Siemens SENTRON 3VA2440-5HN32-0CL0 molded case circuit breaker, 400 A rated continuous current, 3-pole, ETU350 electronic trip unit, line protection. Breaking capacity 187 kA at 24","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"400 A","at 45 °C":"400 A","at 50 °C":"400 A","at 55 °C":"384 A","at 60 °C":"376 A","at 65 °C":"368 A","at 70 °C":"360 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"66 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"400 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2440-5HN32-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB24","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"400 A","Adjustable response value current / li max.":"4 800 A","Adjustable response value current / li min.":"4 800 A","Adjustable response value current / lr min.":"160 A","Adjustable response value current / Isd max.":"0 A","Adjustable response value current / Isd min.":"0 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"4","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"630 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"35 x 10","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0eb36652ce522f093395d6bd0dd27e34.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=426924&mlfb=3VA2440-5HN32-0CL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2440-5HN32-0CL0/alternatives.json"},"ai":{"faq":[{"question":"Does this breaker include undervoltage protection?","answer":"Yes, an undervoltage release (UVR) is integrated — the breaker trips when control voltage drops below the dropout threshold."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2440-5HN32-0CL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2440-5HN32-0CL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}