{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2440-5HN32-0JC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2440-5HN32-0JC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2440-5HN32-0JC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2440-5HN32-0JC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2440-5HN32-0JC0, 3-pole molded case circuit breaker, 400 A continuous at 40-70 °C, 4800 A frame, interrupting capacity 187 kA at 240 V, 121 kA at 415/440 V, 75.6 kA at 500 V, 9 kA at 690 V.","salesMarkdown":"## Siemens 3VA2440-5HN32-0JC0 — 400 A SENTRON MCCB with 4800 A Frame The Siemens SENTRON 3VA2440-5HN32-0JC0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current of 400 A across the full 40 °C to 70 °C ambient range — no derating needed up to that ceiling. The 4800 A frame size gives it the mechanical and thermal capacity to handle high-fault scenarios, with interrupting ratings of 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 9 kA at 690 V. That 187 kA at 240 V is the headline number for North American 240 V delta services; the 121 kA at 415 V covers the common European 400 V class. ## Built-in Accessories and Variant Structure The base switch variant is 3VA2440-5HN32-0AA0, meaning the -0JC0 suffix adds the shunt trip and aux switches as a pre-configured assembly. ## Electrical and Environmental Limits Maximum power loss is 63.5 W — relevant for thermal management inside a sealed enclosure; ensure adequate ventilation or derating if multiple breakers are ganged.","metaTitle":"Siemens 3VA2440-5HN32-0JC0 SENTRON MCCB, 400 A, 4800 A frame","metaDescription":"Siemens SENTRON 3VA2440-5HN32-0JC0 molded case circuit breaker, 3-pole, 400 A continuous rating, 4800 A frame, 187 kA at 240 V. Current lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"4 800 A","Minimum":"4 800 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"9 kA","at 40 °C":"400 A","at 45 °C":"400 A","at 50 °C":"400 A","at 55 °C":"400 A","at 60 °C":"400 A","at 65 °C":"400 A","at 70 °C":"400 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Limited To 1 S":"5 kA","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"63.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2440-5HN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"400 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"630 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0eb36652ce522f093395d6bd0dd27e34.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=461296&mlfb=3VA2440-5HN32-0JC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2440-5HN32-0JC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2440-5HN32-0JC0 and get current pricing?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the interrupting capacity of 3VA2440-5HN32-0JC0 at different voltages?","answer":"At 240 V it interrupts 187 kA; at 415 V and 440 V, 121 kA; at 500 V, 75.6 kA; at 690 V, 9 kA. The 4800 A frame supports these high-fault ratings."},{"question":"What accessories are included on this variant?","answer":"This variant includes a factory-fitted shunt trip (STL) auxiliary release and two HQ auxiliary switches. No undervoltage release or ground-fault monitoring."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2440-5HN32-0JC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2440-5HN32-0JC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}