{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2440-5MP32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2440-5MP32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2440-5MP32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2440-5MP32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2440-5MP32-0AA0, 3-pole molded case circuit breaker for motor protection, 400 A continuous, 187 kA interrupting at 240 V.","salesMarkdown":"The Siemens 3VA2440-5MP32-0AA0 is a SENTRON 3-pole molded case circuit breaker (MCCB) designed specifically for motor protection, rated at 400 A continuous current with no derating across the full 40 °C to 70 °C ambient range — that means the same 400 A rating holds in a hot panel or a conditioned room, no compensation factor to apply. Interrupting capacity hits 187 kA at 240 V, 121 kA at 415/440 V, 75.6 kA at 500 V, and 9 kA at 690 V — the 187 kA figure at 240 V is the headline number for high-fault panelboards; the 121 kA at 415 V is what matters for most European 400 V industrial distribution. Built-in phase failure detection and communication function are onboard, so it can report status to a PLC or BMS without an add-on module. ## Sizing and SCCR fit The 400 A frame is the largest in the 3VA2 family before stepping to the 3VA3 series — verify the mounting footprint matches your existing busbar layout if swapping from a different brand. Maximum power loss of 63.5 W means ventilation in the enclosure matters at full load; the breaker itself runs warm but within spec. ## Lifecycle and procurement This is the standard catalog part for new panel builds, not a sunset line.","metaTitle":"Siemens 3VA2440-5MP32-0AA0 SENTRON MCCB, 400 A, 3-Pole, Moto","metaDescription":"Siemens 3VA2440-5MP32-0AA0 SENTRON molded case circuit breaker. 400 A continuous, 3-pole motor protection. SCCR 187 kA at 240 V. Current production. Request quote for pricing and a","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"25 s","Minimum":"3 s","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"9 kA","at 40 °C":"400 A","at 45 °C":"400 A","at 50 °C":"400 A","at 55 °C":"400 A","at 60 °C":"400 A","at 65 °C":"400 A","at 70 °C":"400 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Limited To 1 S":"5 kA","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Motor protection","Communication Function":"Yes","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"63.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"400 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10/10E, 20/ 20E, 30/30E","Design Of The Overcurrent Release":"ETU550M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"90 000 W","operating power / at AC-3 / at 400 V":"160 000 W","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"630 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0eb36652ce522f093395d6bd0dd27e34.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1133452&mlfb=3VA2440-5MP32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2440-5MP32-0AA0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2440-5MP32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2440-5MP32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}