{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2440-6HL32-0CA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2440-6HL32-0CA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2440-6HL32-0CA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2440-6HL32-0CA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2440-6HL32-0CA0, 3-pole molded case circuit breaker, rated continuous current 400 A, line protection, ETU320 overcurrent release, undervoltage release, interrupting ratings up to 242 kA at 240 V.","salesMarkdown":"## 400 A MCCB with ETU320 — interrupting capacity and thermal derating The breaker carries the full 400 A up to 50 °C ambient; above that, derate to 384 A at 55 °C, 376 A at 60 °C, 368 A at 65 °C, and 360 A at 70 °C (–). Maximum power loss is 66 W. ## Panel integration — dimensions and mounting ## Interrupting ratings at system voltages Rated short-circuit breaking capacity: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 40 kA at 690 V (–). These values cover most industrial distribution voltages up to 690 V.","metaTitle":"Siemens 3VA2440-6HL32-0CA0 SENTRON MCCB, 400 A, 3-Pole, Line","metaDescription":"Siemens SENTRON 3VA2440-6HL32-0CA0 molded case circuit breaker, 400 A rated continuous current, 3-pole, line protection, ETU320 release. Active lifecycle, sourced to order against","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"40 kA","at 40 °C":"400 A","at 45 °C":"400 A","at 50 °C":"400 A","at 55 °C":"384 A","at 60 °C":"376 A","at 65 °C":"368 A","at 70 °C":"360 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"66 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"400 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2440-6HL32-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB24","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"400 A","Adjustable response value current / li max.":"4 800 A","Adjustable response value current / li min.":"600 A","Adjustable response value current / lr min.":"160 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"630 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"35 x 10","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0eb36652ce522f093395d6bd0dd27e34.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=14877&mlfb=3VA2440-6HL32-0CA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2440-6HL32-0CA0/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source for 3VA2440-6HL32-0CA0?","answer":"The peer MPN 3VA1112-5EF32-0CA0 is a smaller-frame 3VA SENTRON MCCB but with a lower continuous current rating and different interrupting capacity — it will not drop into the same panel without verifying the frame size, lug kit, and interrupting requirements. No direct second-source exists; the 3VA2440 frame is specific to the 400 A rating."},{"question":"Where can I buy 3VA2440-6HL32-0CA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What are the interrupting ratings of 3VA2440-6HL32-0CA0?","answer":"242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 40 kA at 690 V (–)."},{"question":"What compliance documentation does Siemens provide for 3VA2440-6HL32-0CA0?","answer":"Siemens typically provides RoHS, REACH, UL, and IEC compliance documentation for the SENTRON 3VA series. Specific certificates should be requested at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2440-6HL32-0CA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2440-6HL32-0CA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}