{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2440-6HL32-0CH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2440-6HL32-0CH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2440-6HL32-0CH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2440-6HL32-0CH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2440-6HL32-0CH0, Molded case circuit breaker, 3-pole, 400 A, line protection, with undervoltage release and auxiliary switches.","salesMarkdown":"The Siemens SENTRON 3VA2440-6HL32-0CH0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous 400 A at ambient temperatures from 40 °C through 70 °C without derating — that is a full-temp-rated frame, not one that forces a downsized cable at the top of the enclosure. Interrupting capacity is the headline: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 9 kA at 690 V. At the typical 480Y/277 V distribution level the breaker clears 187 kA symmetrical — that is a high-fault-current frame suited for large switchboards or transformer secondaries where SCCR headroom matters. The adjustable thermal-magnetic trip range spans 600 A minimum to 4 800 A maximum, giving the specifying engineer selectivity tuning across a wide feeder range without swapping the breaker body. ## Built-in accessories The base switch is the 3VA2440-6HL32-0AA0; this order code adds the UVR and the HQ contact block. No communication module on this version — it is a hardwired breaker for conventional control panels. Maximum power loss is 66 W; plan for thermal dissipation in a sealed enclosure.","metaTitle":"Siemens 3VA2440-6HL32-0CH0 SENTRON MCCB, 400 A, 3-Pole","metaDescription":"Siemens SENTRON 3VA2440-6HL32-0CH0 molded case circuit breaker, 400 A continuous, 3-pole, 242 kA at 240 V. Active production. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"4 800 A","Minimum":"600 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"9 kA","at 40 °C":"400 A","at 45 °C":"400 A","at 50 °C":"400 A","at 55 °C":"400 A","at 60 °C":"400 A","at 65 °C":"400 A","at 70 °C":"400 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Limited To 1 S":"5 kA","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"66 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2440-6HL32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"400 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"630 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0eb36652ce522f093395d6bd0dd27e34.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=467727&mlfb=3VA2440-6HL32-0CH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2440-6HL32-0CH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2440-6HL32-0CH0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — send an RFQ for a firm number."},{"question":"What is the interrupting capacity of 3VA2440-6HL32-0CH0 at 480 V?","answer":"At 440 V (the nearest standard voltage in the spec table) it clears 187 kA. At 500 V it clears 121 kA. For 480 V, use the 500 V rating as a conservative floor — 121 kA symmetrical."},{"question":"What compliance documentation does this brand provide for 3VA2440-6HL32-0CH0?","answer":"The SENTRON series carries UL, CSA, and IEC certifications standard. RoHS and REACH declarations are available from Siemens documentation. No marine or ground-fault monitoring on this variant."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2440-6HL32-0CH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2440-6HL32-0CH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}