{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2440-6HN32-0JL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2440-6HN32-0JL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2440-6HN32-0JL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2440-6HN32-0JL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2440-6HN32-0JL0, molded case circuit breaker, 3-pole, 400 A rated, 242 kA at 240 V, line protection design.","salesMarkdown":"That makes it a straight drop-in for a 400 A bus or feeder that sees a warm enclosure. Breaking capacity sits at 242 kA at 240 V, 187 kA at 415/440 V, and 121 kA at 500 V; at 690 V it still clears 9 kA. For a line-side fault with those SCCR numbers, this breaker holds coordination without upstream fuses in most industrial panels. That's a standard SENTRON 3VA2 frame footprint — it occupies the same cutout as other 3VA2 breakers in the 400 A class. The 3-pole construction with line protection design means it's set up for feeder or main breaker duty, not motor circuit protection. ## Auxiliaries and releases If you need remote status or emergency trip, the wiring points are already there; if you need UVR or GF, this isn't the right order code. ## Environmental and storage The storage maximum is the handling limit, not the running limit — the breaker can sit in a cold truck or hot container without damage.","metaTitle":"Siemens 3VA2440-6HN32-0JL0 SENTRON MCCB, 400 A, 242 kA","metaDescription":"Siemens SENTRON 3VA2440-6HN32-0JL0 molded case circuit breaker, 400 A rated, 242 kA at 240 V, 3-pole, line protection. Current production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"4 800 A","Minimum":"4 800 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"9 kA","at 40 °C":"400 A","at 45 °C":"400 A","at 50 °C":"400 A","at 55 °C":"400 A","at 60 °C":"400 A","at 65 °C":"400 A","at 70 °C":"400 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Limited To 1 S":"5 kA","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"63.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2440-6HN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"400 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"630 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0eb36652ce522f093395d6bd0dd27e34.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=329761&mlfb=3VA2440-6HN32-0JL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2440-6HN32-0JL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2440-6HN32-0JL0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What are the key ratings on this MCCB?","answer":"Rated 400 A continuous from 40 °C to 70 °C with no derating. Breaking capacity is 242 kA at 240 V, 187 kA at 415/440 V, 121 kA at 500 V, and 9 kA at 690 V."},{"question":"What is the physical size of this breaker?","answer":"248 mm high × 138 mm wide × 110 mm deep — standard SENTRON 3VA2 frame footprint."},{"question":"Does this breaker include a shunt trip or undervoltage release?","answer":"It includes a factory-fitted shunt trip (STL) for remote tripping. No undervoltage release is fitted."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2440-6HN32-0JL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2440-6HN32-0JL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}