{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2440-7HN32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2440-7HN32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2440-7HN32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2440-7HN32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2440-7HN32-0AA0, molded case circuit breaker, 3-pole, 400 A, ETU350 electronic trip unit, 330 kA breaking capacity at 240 V AC.","salesMarkdown":"## MCCB for main feeder or large motor protection The Siemens SENTRON 3VA2440-7HN32-0AA0 is a molded case circuit breaker rated for 400 A continuous current — no derating needed from 40 °C up through 70 °C, so it holds its full rating even in a warm enclosure. Breaking capacity sits at 330 kA at 240 V AC, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 9 kA at 690 V. The 3VA2440-7HN32-0AA0 measures 248 mm tall, 138 mm wide, and 110 mm deep. That 138 mm width is the standard 3-pole MCCB footprint for this frame size — it bolts into the same mounting pattern as other SENTRON 3VA breakers in the 400 A class, so swapping one in doesn't mean redrilling the backplate or reworking bus bars.","metaTitle":"Siemens 3VA2440-7HN32-0AA0 SENTRON MCCB, 400 A, 3-pole, 330","metaDescription":"Siemens SENTRON 3VA2440-7HN32-0AA0 molded case circuit breaker. 400 A continuous, 3-pole, ETU350 release. Breaking capacity 330 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"4 800 A","Minimum":"4 800 A","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"9 kA","at 40 °C":"400 A","at 45 °C":"400 A","at 50 °C":"400 A","at 55 °C":"400 A","at 60 °C":"400 A","at 65 °C":"400 A","at 70 °C":"400 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Limited To 1 S":"5 kA","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"63.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"400 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"630 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0eb36652ce522f093395d6bd0dd27e34.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=530726&mlfb=3VA2440-7HN32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2440-7HN32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2440-7HN32-0AA0 at different voltages?","answer":"330 kA at 240 V AC, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 9 kA at 690 V. The 240 V rating covers most service-entrance applications without needing a current-limiting fuse."},{"question":"What trip unit does the 3VA2440-7HN32-0AA0 use?","answer":"It uses the ETU350 electronic trip unit, which provides adjustable long-time, short-time, instantaneous, and ground-fault protection curves for coordination selectivity."},{"question":"Who supplies 3VA2440-7HN32-0AA0 and how is it quoted?","answer":"This part is sourced through independent industrial distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — no stock figures or lead-time numbers are published here."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2440-7HN32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2440-7HN32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}