{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2450-5MN32-0CC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2450-5MN32-0CC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2450-5MN32-0CC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2450-5MN32-0CC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2450-5MN32-0CC0, 3-pole, 500 A, ETU350M electronic trip unit, 187 kA at 240 VAC.","salesMarkdown":"The 3VA2450-5MN32-0CC0: Breaking capacity runs 187 kA at 240 VAC, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V — so the 240 V figure tells you this breaker handles the high available fault current typical of step-down transformer secondaries, while the 690 V rating confirms it clears faults on 690 V line-fed drives without cascading upstream. Current derating is flat at 500 A from 40 °C through 50 °C, then drops to 495 A at 55 °C, 490 A at 60 °C, 485 A at 65 °C, and 480 A at 70 °C. That means in a hot panel — say 55 °C ambient — you lose only 5 A; the breaker still carries a 495 A load without nuisance tripping. ## Trip unit and protection features That is a common requirement for safety circuits and emergency-stop chains in machinery panels. ## Mechanical fit and environmental limits The 15 000 mechanical endurance cycles (latching) suit frequent-switching applications like compressor or pump motor feeders.","metaTitle":"Siemens 3VA2450-5MN32-0CC0 SENTRON MCCB, 500 A, 187 kA at 24","metaDescription":"Siemens 3VA2450-5MN32-0CC0 SENTRON molded case circuit breaker, 500 A rated, 3-pole, ETU350M release, 187 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"500 A","at 45 °C":"500 A","at 50 °C":"500 A","at 55 °C":"495 A","at 60 °C":"490 A","at 65 °C":"485 A","at 70 °C":"480 A","Trip indicator":"No","Number of poles":"3","Product version":"Motor protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"101.5 W","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"500 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2450-5MN32-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB24","Design of the overcurrent release":"ETU350M","Protection class IP / on the front":"IP40","Operating power / at AC-3 / at 400 V":"200 W","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"15","Adjustable response value time / tr min.":"4","Adjustable response value time / tsd max.":"0.03 s","Adjustable response value time / tsd min.":"0.03 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"500 A","Adjustable response value current / li max.":"7 500 A","Adjustable response value current / li min.":"7 500 A","Adjustable response value current / lr min.":"200 A","Adjustable response value current / Isd max.":"7 500 A","Adjustable response value current / Isd min.":"1 500 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"630 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570122&mlfb=3VA2450-5MN32-0CC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2450-5MN32-0CC0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2450-5MN32-0CC0 at 240 V?","answer":"187 kA at 240 VAC, which covers the high fault current available on step-down transformer secondaries in industrial distribution."},{"question":"What trip unit does this MCCB use?","answer":"It uses the ETU350M electronic overcurrent release with adjustable LSI protection curves and built-in phase failure detection."},{"question":"Where can I buy 3VA2450-5MN32-0CC0 and how is it quoted?","answer":"This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time."},{"question":"Does 3VA2450-5MN32-0CC0 include an undervoltage release?","answer":"Yes, an undervoltage release (UVR) is integrated as standard in this order code variant."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2450-5MN32-0CC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2450-5MN32-0CC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}