{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2450-5MN32-0CH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2450-5MN32-0CH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2450-5MN32-0CH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2450-5MN32-0CH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2450-5MN32-0CH0, molded case circuit breaker, 3-pole, 500 A at 40 °C, motor protection design, 187 kA at 240 V interrupting capacity.","salesMarkdown":"The interrupting capacity reaches 187 kA at 240 V, stepping down to 121 kA at 415/440 V and 75.6 kA at 500 V — at 690 V it still holds 9 kA. That's enough headroom for most industrial distribution panels feeding motor control centers. ## What the built-in components mean for a panel swap That means no extra wiring for a shunt trip or aux contact block — the UVR drops the breaker if control voltage fails, and the alarm switch signals a trip condition back to the PLC or annunciator. Phase failure detection is also built in, so it catches a lost phase before the motor cooks. The auxiliary release is a UVR, not a shunt trip — if your circuit needs a remote trip from a pushbutton or safety relay, you'd add a shunt trip separately.","metaTitle":"Siemens 3VA2450-5MN32-0CH0 SENTRON MCCB, 500 A, 3-Pole, Moto","metaDescription":"Siemens SENTRON 3VA2450-5MN32-0CH0 molded case circuit breaker, 500 A at 40 °C, 3-pole, motor protection design. 187 kA at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"13 s","Minimum":"4 s","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"9 kA","at 40 °C":"500 A","at 45 °C":"500 A","at 50 °C":"500 A","at 55 °C":"495 A","at 60 °C":"490 A","at 65 °C":"485 A","at 70 °C":"480 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Limited To 1 S":"6 kA","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"101.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2450-5MN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"500 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"110 000 W","operating power / at AC-3 / at 400 V":"200 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"630 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570123&mlfb=3VA2450-5MN32-0CH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2450-5MN32-0CH0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2450-5MN32-0CH0?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time from independent distribution — no automated figure here is reliable for a buying decision."},{"question":"What compliance documentation does this breaker carry?","answer":"The SENTRON series is designed to meet IEC 60947-2 and UL 489 standards for molded case circuit breakers. Specific certification marks (CE, UL, CSA) are typically listed on the nameplate; the datasheet and declaration of conformity are available from Siemens on request."},{"question":"Will 3VA2450-5MN32-0CH0 drop into a panel specified around 3VA2116-5JP32-0AE0 without rewiring?","answer":"Not directly — the 3VA2450 is a 500 A frame, while the 3VA2116 is a 160 A frame. The physical footprint (width, depth, mounting hole pattern) differs between frame sizes. You'd need to verify panel cutout dimensions and bus bar spacing before assuming a drop-in swap."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2450-5MN32-0CH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2450-5MN32-0CH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}