{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2450-5MN32-0JC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2450-5MN32-0JC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2450-5MN32-0JC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2450-5MN32-0JC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2450-5MN32-0JC0, molded case circuit breaker, motor protection design, 3-pole, 500 A at 40 °C, interrupting capacity 187 kA at 240 V.","salesMarkdown":"Rated 500 A continuously at ambient temperatures up to 50 °C without derating; above that, the thermal capacity steps down per the datasheet: 495 A at 55 °C, 490 A at 60 °C, 485 A at 65 °C, and 480 A at 70 °C. For a panel that runs warm — say, adjacent to drives or transformers — the 55 °C derating is the first threshold to check against your motor FLA. Interrupting capacity is substantial at the lower voltage tiers: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 9 kA at 690 V. Footprint is 138 mm wide by 248 mm tall by 110 mm deep — a 3-pole frame that fits standard MCCB panel cutouts. The depth of 110 mm (4.33 in) is the dimension from the mounting surface to the front of the breaker; verify clearance for the shunt trip (STL) and the two HQ auxiliary switches that come fitted on this variant. Maximum power loss is 99 W at rated load — that heat has to be managed inside the enclosure. For a sealed panel with multiple breakers ganged, factor the dissipation into your thermal budget.","metaTitle":"Siemens 3VA2450-5MN32-0JC0 SENTRON MCCB, 500 A, 3-Pole, Moto","metaDescription":"Siemens 3VA2450-5MN32-0JC0 SENTRON molded case circuit breaker, 500 A at 40 °C, 3-pole, motor protection design, 187 kA at 240 V. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"13 s","Minimum":"4 s","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"9 kA","at 40 °C":"500 A","at 45 °C":"500 A","at 50 °C":"500 A","at 55 °C":"495 A","at 60 °C":"490 A","at 65 °C":"485 A","at 70 °C":"480 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Limited To 1 S":"6 kA","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"99 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2450-5MN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"500 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"110 000 W","operating power / at AC-3 / at 400 V":"200 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"630 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570134&mlfb=3VA2450-5MN32-0JC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2450-5MN32-0JC0/alternatives.json"},"ai":{"faq":[{"question":"Does the 3VA2450-5MN32-0JC0 include phase failure detection and auxiliary switches?","answer":"Yes, it includes phase failure detection, two HQ auxiliary switches, and a shunt trip (STL) release. It does not include an undervoltage release or communication function."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2450-5MN32-0JC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2450-5MN32-0JC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}