{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2450-5MP32-0AE0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2450-5MP32-0AE0","canonicalUrl":"https://aoctrl.com/siemens/3VA2450-5MP32-0AE0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2450-5MP32-0AE0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA2 IEC Frame 630, breaking capacity class M, Icu=55kA @ 415V, 3-pole, motor protection ETU550M, LSI, In=500A, overload IR=200-500A, short-circuit Isd=1.2-15x In, Ii=3-15x In, busbar connection, 4 auxiliary switch changeover.","salesMarkdown":"Siemens 3VA2450-5MP32-0AE0 is a 3-pole IEC motor protection circuit breaker on the 3VA2 Frame 630 platform. Rated In=500A with an ETU550M LSI trip unit — overload adjustable 200-500A, short-circuit pickup Isd=1.2-15x In and instantaneous Ii=3-15x In. Busbar connection and four auxiliary switch changeovers are built in.","metaTitle":"Siemens 3VA2450-5MP32-0AE0 Circuit Breaker, 55kA @ 415V","metaDescription":"Siemens 3VA2450-5MP32-0AE0 IEC 3-pole motor protection breaker, 500A, ETU550M LSI, breaking capacity class M Icu=55kA @ 415V. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1535739&mlfb=3VA2450-5MP32-0AE0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2450-5MP32-0AE0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2450-5MP32-0AE0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing."},{"question":"What is 3VA2450-5MP32-0AE0's listed breaking capacity?","answer":"Breaking capacity class M with Icu=55kA @ 415V — sufficient for high-fault industrial motor circuits."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2450-5MP32-0AE0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2450-5MP32-0AE0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}