{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2450-7MN32-0AJ0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2450-7MN32-0AJ0","canonicalUrl":"https://aoctrl.com/siemens/3VA2450-7MN32-0AJ0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2450-7MN32-0AJ0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2450-7MN32-0AJ0, molded case circuit breaker, 3-pole, motor protection design, 500 A at 40 °C, breaking capacity 330 kA at 240 V.","salesMarkdown":"It is rated 500 A continuously at 40 °C, with the same rating holding through 50 °C before a gentle derate begins — 495 A at 55 °C, 490 A at 60 °C, 485 A at 65 °C, 480 A at 70 °C. Breaking capacity is 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 15.3 kA at 690 V. The short-time withstand (Icw) is 6 kA limited to 1 second — that figure governs selectivity with downstream breakers during a fault. For motor starting duty, the adjustable time-delay settings (minimum 4 s, maximum 13 s) let you ride through inrush without nuisance trips. No undervoltage release or communication module is fitted from the factory — those are add-on options if the application needs them. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C — cold-storage and freezer environments are within the operating envelope as long as the ambient stays above -25 °C. Maximum power loss is 99 W. That is the heat the breaker dissipates at full rated current — factor it into the enclosure thermal calculation, especially in a sealed NEMA 4X or IP65 cabinet where convection is limited.","metaTitle":"Siemens 3VA2450-7MN32-0AJ0 SENTRON MCCB, 500 A, 3-Pole, Moto","metaDescription":"Siemens SENTRON 3VA2450-7MN32-0AJ0 molded case circuit breaker, 500 A at 40 °C, 3-pole, motor protection design. Breaking capacity 330 kA at 240 V. Active production. Quoted to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"13 s","Minimum":"4 s","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"15.3 kA","at 40 °C":"500 A","at 45 °C":"500 A","at 50 °C":"500 A","at 55 °C":"495 A","at 60 °C":"490 A","at 65 °C":"485 A","at 70 °C":"480 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Limited To 1 S":"6 kA","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"99 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2450-7MN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HP","Design Of The Auxiliary Release":"Without auxiliary release","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"500 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"110 000 W","operating power / at AC-3 / at 400 V":"200 000 W","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"630 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB11","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570148&mlfb=3VA2450-7MN32-0AJ0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2450-7MN32-0AJ0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this MCCB at 415 V?","answer":"The breaking capacity is 242 kA at 415 V, matching the rating at 440 V. At 240 V it reaches 330 kA, and at 690 V it is 15.3 kA."},{"question":"Will 3VA2450-7MN32-0AJ0 drop into a panel specified around 3VA1110-5EF32-0AM0 without rewiring?","answer":"No — the 3VA2450-7MN32-0AJ0 is a 500 A frame on a different physical footprint than the 3VA1110-5EF32-0AM0. Panel cutouts and bus bar spacing differ; a direct mechanical swap is not possible without modifying the mounting and connections."},{"question":"Where can I buy 3VA2450-7MN32-0AJ0 and what is the lead time?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead-time and price commitment."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2450-7MN32-0AJ0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2450-7MN32-0AJ0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}