{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2463-5HN32-0JA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2463-5HN32-0JA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2463-5HN32-0JA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2463-5HN32-0JA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2463-5HN32-0JA0, molded case circuit breaker, 3-pole, 630 A, 187 kA at 240 V, ETU350 release, shunt trip.","salesMarkdown":"Its interrupting capacity hits 187 kA at 240 V, 121 kA at 415/440 V, 75.6 kA at 500 V, and 17 kA at 690 V — figures that give selectivity headroom for high-fault utility feeds or transformer secondaries. The 630 A rating at 40 °C derates to 520 A at 70 °C — a 17 % drop that matters when the breaker sits in a crowded, poorly ventilated enclosure. ## Integration notes The ETU350 trip unit is field-configurable for LSI curves; the shunt trip (STL) requires a separate control voltage. No auxiliary contacts or communication module are built in — add the 3VA9688-0BL32 auxiliary trip block if you need remote status. The maximum power loss of 162 W must be factored into enclosure thermal calculations.","metaTitle":"Siemens 3VA2463-5HN32-0JA0 SENTRON MCCB, 630 A, 187 kA at 24","metaDescription":"Siemens SENTRON 3VA2463-5HN32-0JA0 molded case circuit breaker, 630 A rated, 187 kA breaking at 240 V. ETU350 release, shunt trip. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"630 A","at 45 °C":"612 A","at 50 °C":"593 A","at 55 °C":"575 A","at 60 °C":"557 A","at 65 °C":"538 A","at 70 °C":"520 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"162 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"630 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2463-5HN32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"12","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"630 A","Adjustable response value current / li max.":"5 670 A","Adjustable response value current / li min.":"5 670 A","Adjustable response value current / lr min.":"250 A","Adjustable response value current / Isd max.":"0 A","Adjustable response value current / Isd min.":"0 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"630 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"35 x 10","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ff193dd53a0856db1ca969741fab18b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=315060&mlfb=3VA2463-5HN32-0JA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2463-5HN32-0JA0/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for 3VA2463-5HN32-0JA0?","answer":"Rated continuous current Iu of 630 A, breaking capacity of 187 kA at 240 V, 121 kA at 415/440 V, and 800 V rated insulation voltage. The ETU350 electronic trip unit provides LSI protection."},{"question":"Where can I buy 3VA2463-5HN32-0JA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."},{"question":"Does 3VA2463-5HN32-0JA0 include a shunt trip?","answer":"Yes, it is designed with a shunt trip (STL) auxiliary release for remote tripping capability."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2463-5HN32-0JA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2463-5HN32-0JA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}