{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2463-5HN32-0KL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2463-5HN32-0KL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2463-5HN32-0KL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2463-5HN32-0KL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2463-5HN32-0KL0, molded case circuit breaker, 630 A continuous, 3-pole, 187 kA interrupting at 240 V, line protection design, shunt trip release, 2 auxiliary switches + 1 trip alarm + 1 electrical alarm switch HQ.","salesMarkdown":"The interrupting capacity hits 187 kA at 240 V, drops to 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 9 kA at 690 V. At 45 °C it derates to 612 A, at 50 °C to 593 A, at 55 °C to 575 A, at 60 °C to 557 A, at 65 °C to 538 A, and at 70 °C to 520 A. Plan the load accordingly. That 138 mm width across three poles is standard for a 630 A frame. Max power loss is 162 W. The storage limits are wider because the breaker isn't carrying current — that's the handling spec, not the running spec. ## What the auxiliary switch complement means for your control wiring That's four separate signal paths — enough for a PLC input, a status lamp, a remote SCADA point, and a spare. The shunt trip (STL) allows remote tripping by applying a control voltage. No undervoltage release is fitted, so the breaker won't automatically open on loss of control power — that's a deliberate choice for applications where you want the load to stay online even if the control supply drops. Trip indicator is present — a mechanical flag visible on the front of the breaker shows whether it tripped on fault or was manually switched off. Helps the maintenance tech distinguish a real event from a test or isolation.","metaTitle":"Siemens 3VA2463-5HN32-0KL0 MCCB, 630 A, 3-Pole, 187 kA at 24","metaDescription":"Siemens SENTRON 3VA2463-5HN32-0KL0 molded case circuit breaker, 630 A continuous, 3-pole, 187 kA interrupting at 240 V. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"5 670 A","Minimum":"5 670 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"9 kA","at 40 °C":"630 A","at 45 °C":"612 A","at 50 °C":"593 A","at 55 °C":"575 A","at 60 °C":"557 A","at 65 °C":"538 A","at 70 °C":"520 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"162 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2463-5HN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"630 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"630 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ff193dd53a0856db1ca969741fab18b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=11050&mlfb=3VA2463-5HN32-0KL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2463-5HN32-0KL0/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does this brand provide for 3VA2463-5HN32-0KL0?","answer":"As a Siemens SENTRON product, it carries the standard IEC/UL certifications for molded case circuit breakers. Specific compliance documentation (RoHS, REACH, UL, IEC) is available upon request with the RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2463-5HN32-0KL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2463-5HN32-0KL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}