{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2463-5JP32-0DL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2463-5JP32-0DL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2463-5JP32-0DL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2463-5JP32-0DL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2463-5JP32-0DL0, molded case circuit breaker, 3-pole, 630 A continuous rated current, 187 kA breaking capacity at 240 V AC, line protection design with communication function and undervoltage release.","salesMarkdown":"At 415 V and 440 V it still holds 121 kA, dropping to 75.6 kA at 500 V and 9 kA at 690 V — so the voltage class of your system directly governs the available short-circuit protection. The unit includes a built-in undervoltage release and a communication function for integration with higher-level monitoring systems. The continuous current rating is temperature-dependent: 630 A at 40 °C, derating to 450 A at 70 °C. The 110 mm depth, 138 mm width, and 248 mm height fit standard MCCB mounting footprints in switchgear; the 164.5 W maximum power loss must be factored into enclosure ventilation calculations.","metaTitle":"Siemens 3VA2463-5JP32-0DL0 SENTRON MCCB, 630 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA2463-5JP32-0DL0 molded case circuit breaker, 630 A continuous, 3-pole, 187 kA at 240 V. Current lifecycle. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"5 670 A","Minimum":"945 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"9 kA","at 40 °C":"630 A","at 45 °C":"600 A","at 50 °C":"570 A","at 55 °C":"540 A","at 60 °C":"510 A","at 65 °C":"480 A","at 70 °C":"450 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"164.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2463-5JP32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"630 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"630 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ff193dd53a0856db1ca969741fab18b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=424079&mlfb=3VA2463-5JP32-0DL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2463-5JP32-0DL0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2463-5JP32-0DL0?","answer":"This part is sourced and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time through our independent distribution network."},{"question":"What is 3VA2463-5JP32-0DL0's listed depth?","answer":"The depth is 110 mm (4.33 in)."},{"question":"What is 3VA2463-5JP32-0DL0's listed width?","answer":"The width is 138 mm (5.43 in)."},{"question":"Will 3VA2463-5JP32-0DL0 drop into a panel that was specified around 3VA2225-5HN42-0BB0 without rewiring?","answer":"The 3VA2463-5JP32-0DL0 is a 3-pole 630 A MCCB with a 110 mm depth, 138 mm width, and 248 mm height. The 3VA2225-5HN42-0BB0 is a different rating within the same SENTRON family, so physical footprint and terminal spacing may differ. Verify the mounting dimensions and bus bar alignment against your existing panel layout before assuming a direct swap."},{"question":"What compliance documentation does this brand provide for 3VA2463-5JP32-0DL0 (RoHS, REACH, UL, IEC)?","answer":"As a Siemens SENTRON product, this MCCB is designed to meet applicable IEC and UL standards for molded case circuit breakers. Specific RoHS and REACH declarations are available from the manufacturer upon request. The evidence does not list individual certification marks, so confirm the exact compliance package needed for your jurisdiction at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2463-5JP32-0DL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2463-5JP32-0DL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}