{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2463-5JQ32-0AF0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2463-5JQ32-0AF0","canonicalUrl":"https://aoctrl.com/siemens/3VA2463-5JQ32-0AF0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2463-5JQ32-0AF0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, Molded case circuit breaker, 3VA2463-5JQ32-0AF0, 3-pole, 630 A, line protection, ETU560, 187 kA at 240 V.","salesMarkdown":"The Siemens 3VA2463-5JQ32-0AF0 is a 3-pole SENTRON molded case circuit breaker rated for 630 A continuous current at 40 °C, with an ETU560 electronic trip unit for line protection. At 415 V and 440 V it still holds 121 kA, dropping to 75.6 kA at 500 V and 17 kA at 690 V, so the SCCR headroom is substantial for most industrial distribution boards. Thermal derating is built into the rating table: at 45 °C it carries 600 A, at 50 °C 570 A, at 55 °C 540 A, at 60 °C 510 A, at 65 °C 480 A, and at 70 °C 450 A. The 110 mm depth, 138 mm width, and 248 mm height fit typical 600 mm deep switchboards; verify gland-plate clearance for the 162 W maximum power loss if the breaker is enclosed with other heat sources. ## Lifecycle and sourcing — active, quoted to order The integrated auxiliary release is order code 3VA9608-0BB11, and the supplied basic switch is 3VA2463-5JQ32-0AA0 — these are the internal subcomponents, not field-replaceable spares. For external auxiliary contacts, the breaker ships with 1 auxiliary switch + 1 trip alarm switch HQ. ## Integration notes — communication, ground fault, and trip unit The ETU560 trip unit includes a communication function for integration with plant monitoring systems — no separate module needed for basic data. Ground fault monitoring uses summation current formation on the L-conductor, which detects leakage without a separate core-balance CT. Mechanical endurance is rated at 15 000 cycles. The trip indicator gives a local visual flag after a fault trip — useful for troubleshooting without opening the panel.","metaTitle":"Siemens 3VA2463-5JQ32-0AF0 SENTRON MCCB, 630 A, 3-Pole, Line","metaDescription":"Siemens 3VA2463-5JQ32-0AF0 SENTRON MCCB, 630 A rated at 40 °C, 3-pole, line protection with ETU560 trip unit. Breaking capacity 187 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"630 A","at 45 °C":"600 A","at 50 °C":"570 A","at 55 °C":"540 A","at 60 °C":"510 A","at 65 °C":"480 A","at 70 °C":"450 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"Yes","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"162 W","Auxiliary contact version":"1 auxiliary switch + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"630 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2463-5JQ32-0AA0","Design of the auxiliary release":"Without auxiliary release","Ground fault monitoring version":"Summation current formation L-conductor","Of The Integrated Auxiliary Trip":"3VA9608-0BB11","Design of the overcurrent release":"ETU560","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"12","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"630 A","Adjustable response value current / lg max.":"630 A","Adjustable response value current / lg min.":"126 A","Adjustable response value current / li max.":"5 670 A","Adjustable response value current / li min.":"945 A","Adjustable response value current / lr min.":"252 A","Adjustable response value current / Isd max.":"5 670 A","Adjustable response value current / Isd min.":"378 A","Ground fault protection can be switched ON/OFF":"Yes","Neutral conductors / upgradeable/retrofittable":"Yes","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LSIG","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"630 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"35 x 10","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ff193dd53a0856db1ca969741fab18b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=498549&mlfb=3VA2463-5JQ32-0AF0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2463-5JQ32-0AF0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2463-5JQ32-0AF0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote — submit an RFQ for a firm number."},{"question":"What is the depth of 3VA2463-5JQ32-0AF0?","answer":"The depth is 110 mm."},{"question":"What is the width of 3VA2463-5JQ32-0AF0?","answer":"The width is 138 mm."},{"question":"What compliance documentation is available for 3VA2463-5JQ32-0AF0?","answer":"As a Siemens SENTRON MCCB, this part is designed to meet IEC 60947-2 and UL 489 standards. Specific RoHS and REACH declarations are available from the manufacturer upon request. The evidence does not list additional certifications."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2463-5JQ32-0AF0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2463-5JQ32-0AF0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}