{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2463-5JQ32-0CL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2463-5JQ32-0CL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2463-5JQ32-0CL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2463-5JQ32-0CL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2463-5JQ32-0CL0 molded case circuit breaker, 3-pole, 630 A at 40 °C, ETU560 electronic trip unit, 187 kA breaking capacity at 240 V, 110 mm depth, 138 mm width, 248 mm height.","salesMarkdown":"That 630 A figure is the thermal benchmark — above 40 °C you derate linearly: 600 A at 45 °C, 570 A at 50 °C, all the way down to 450 A at 70 °C. For a panel sitting at 50 °C ambient, the real usable current is 570 A, not the headline number. Breaking capacity is the other headline: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V. At 690 V the 17 kA figure is still respectable for most industrial distribution, but if your fault current exceeds that, you'll need a series-rated combination or a higher-rated frame. Maximum power loss of 164.5 W requires accounting for heat dissipation in the enclosure. Mounts in a standard SENTRON panel footprint. The 138 mm width and 110 mm depth leave room for side-mounted accessories. No voltage trigger — that means no shunt trip or undervoltage release as a factory-installed trigger; the UVR is a separate release. Phase failure detection is not built in, so if you need that, you'll rely on the ETU560's phase-loss sensitivity or an external relay.","metaTitle":"Siemens 3VA2463-5JQ32-0CL0 SENTRON MCCB, 630 A, 3-pole, ETU5","metaDescription":"Siemens SENTRON 3VA2463-5JQ32-0CL0 molded case circuit breaker, 630 A at 40 °C, 3-pole, ETU560 release, 187 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"630 A","at 45 °C":"600 A","at 50 °C":"570 A","at 55 °C":"540 A","at 60 °C":"510 A","at 65 °C":"480 A","at 70 °C":"450 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"Yes","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"164.5 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"630 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2463-5JQ32-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Summation current formation L-conductor","Of The Integrated Auxiliary Trip":"3VA9608-0BB24","Design of the overcurrent release":"ETU560","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"12","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"630 A","Adjustable response value current / lg max.":"630 A","Adjustable response value current / lg min.":"126 A","Adjustable response value current / li max.":"5 670 A","Adjustable response value current / li min.":"945 A","Adjustable response value current / lr min.":"252 A","Adjustable response value current / Isd max.":"5 670 A","Adjustable response value current / Isd min.":"378 A","Ground fault protection can be switched ON/OFF":"Yes","Neutral conductors / upgradeable/retrofittable":"Yes","Number of CO contacts / for auxiliary contacts":"4","Protective function of the overcurrent release":"LSIG","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"630 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"35 x 10","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ff193dd53a0856db1ca969741fab18b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=122208&mlfb=3VA2463-5JQ32-0CL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2463-5JQ32-0CL0/alternatives.json"},"ai":{"faq":[{"question":"What is the physical size of 3VA2463-5JQ32-0CL0?","answer":"Depth 110 mm, width 138 mm, height 248 mm."},{"question":"Does this breaker include a ground-fault function?","answer":"Yes, ground-fault monitoring is via summation current formation on the L-conductor (residual-current method), integrated into the ETU560 release."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2463-5JQ32-0CL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2463-5JQ32-0CL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}