{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2463-5JQ32-0HH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2463-5JQ32-0HH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2463-5JQ32-0HH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2463-5JQ32-0HH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2463-5JQ32-0HH0, molded case circuit breaker, 3-pole, 630 A at 40 °C, breaking capacity 187 kA at 240 V AC.","salesMarkdown":"## MCCB for line protection with communication Its 3-pole frame carries a full-scale value of 630 A and an initial pickup of 126 A — the thermal-magnetic trip is set at the factory but field-adjustable within that window. A built-in communication function allows integration into a higher-level energy management system without an external adapter. This MCCB delivers 187 kA at 240 V AC, dropping to 121 kA at 415 V and 440 V, then 75.6 kA at 500 V, and 9 kA at 690 V. The steep fall-off above 500 V is typical for a 630 A frame — the internal arc chamber is optimized for the lower-voltage, high-current faults common in North American 480Y/277 V and European 400 V distribution. ## Thermal derating curve Rated 630 A at 40 °C ambient, the breaker derates linearly: 600 A at 45 °C, 570 A at 50 °C, 540 A at 55 °C, 510 A at 60 °C, 480 A at 65 °C, and 450 A at 70 °C. The maximum power loss is 162 W, which contributes to the enclosure's thermal budget. Dimensions are 248 mm high, 138 mm wide, 110 mm deep — a standard 3-pole MCCB footprint for a 630 A frame. The breaker mounts via four screws to a backplate or DIN-rail adapter (not included). The depth of 110 mm leaves room behind a 200 mm deep enclosure door for wiring and auxiliary wiring. The basic switch variant is 3VA2463-5JQ32-0AA0; this order code adds the shunt trip and communication module.","metaTitle":"Siemens 3VA2463-5JQ32-0HH0 SENTRON MCCB, 630 A, 3-pole","metaDescription":"Siemens 3VA2463-5JQ32-0HH0 SENTRON molded case circuit breaker, 630 A at 40 °C, 3-pole, 187 kA at 240 V. Active production. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"5 670 A","Minimum":"945 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"9 kA","at 40 °C":"630 A","at 45 °C":"600 A","at 50 °C":"570 A","at 55 °C":"540 A","at 60 °C":"510 A","at 65 °C":"480 A","at 70 °C":"450 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Initial Value":"126 A","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Full-Scale Value":"630 A","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"162 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2463-5JQ32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Summation current formation L-conductor","Continuous Current / Rated Value":"630 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU560","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"Yes","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"630 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSIG","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ff193dd53a0856db1ca969741fab18b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=530862&mlfb=3VA2463-5JQ32-0HH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2463-5JQ32-0HH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2463-5JQ32-0HH0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is 3VA2463-5JQ32-0HH0's listed depth (110 mm) on this component line?","answer":"The depth is 110 mm (4.33 in), with a width of 138 mm (5.43 in) and height of 248 mm (9.76 in)."},{"question":"What compliance documentation does this brand provide for 3VA2463-5JQ32-0HH0 (RoHS, REACH, UL, IEC)?","answer":"The SENTRON series is designed to UL 489 and IEC 60947-2 standards. Specific compliance declarations (RoHS, REACH, UL listing) are available from the manufacturer's documentation portal for the exact order code."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2463-5JQ32-0HH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2463-5JQ32-0HH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}