{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2463-5KP32-0AC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2463-5KP32-0AC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2463-5KP32-0AC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2463-5KP32-0AC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2463-5KP32-0AC0, molded case circuit breaker, 3-pole, 630 A continuous at 40 °C, interrupting capacity 187 kA at 240 V AC, 121 kA at 415 V AC.","salesMarkdown":"## Rating and Derating — Continuous Current vs. Ambient Temperature For higher ambient temperatures, the continuous current must be derated per the datasheet curve: 600 A at 45 °C, 570 A at 50 °C, 540 A at 55 °C, 510 A at 60 °C, 480 A at 65 °C, and 450 A at 70 °C. This derating is critical for panel design in non-air-conditioned enclosures or high-heat environments. ## Interrupting Capacity Across Voltage Levels The breaker's interrupting capacity varies with system voltage: 187 kA at 240 V, 121 kA at both 415 V and 440 V, 75.6 kA at 500 V, and 9 kA at 690 V. For audit purposes, the 121 kA rating at 415 V is the figure most commonly referenced in European low-voltage distribution designs per IEC 60947-2. ## Physical Dimensions and Panel Fit The breaker measures 248 mm in height, 138 mm in width, and 110 mm in depth. The 110 mm depth is a key dimension for enclosure depth clearance — verify that the panel door or gland plate allows at least this depth plus wiring bend radius for the line and load conductors.","metaTitle":"Siemens 3VA2463-5KP32-0AC0 SENTRON MCCB, 630 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA2463-5KP32-0AC0 molded case circuit breaker, 630 A continuous at 40 °C, 3-pole, 187 kA interrupting at 240 V. Current lifecycle stage. Available to order against","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"5 670 A","Minimum":"945 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"9 kA","at 40 °C":"630 A","at 45 °C":"600 A","at 50 °C":"570 A","at 55 °C":"540 A","at 60 °C":"510 A","at 65 °C":"480 A","at 70 °C":"450 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"162 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Of The Supplied Basic Switch":"3VA2463-5KP32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"Without auxiliary release","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"630 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"630 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ff193dd53a0856db1ca969741fab18b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=407930&mlfb=3VA2463-5KP32-0AC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2463-5KP32-0AC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2463-5KP32-0AC0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability confirmation."},{"question":"What is 3VA2463-5KP32-0AC0's listed depth?","answer":"The listed depth is 110 mm, which is the dimension from the mounting surface to the front of the breaker."},{"question":"What compliance documentation does this brand provide for 3VA2463-5KP32-0AC0?","answer":"As a SENTRON series MCCB, the 3VA2463-5KP32-0AC0 is designed to meet IEC 60947-2 and UL 489 standards. The manufacturer provides RoHS and REACH declarations on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2463-5KP32-0AC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2463-5KP32-0AC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}