{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2463-6HL32-0CA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2463-6HL32-0CA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2463-6HL32-0CA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2463-6HL32-0CA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2463-6HL32-0CA0, molded case circuit breaker, 3-pole, 630 A continuous at 40 °C, 242 kA breaking capacity at 240 V, with undervoltage release.","salesMarkdown":"The 3VA2463-6HL32-0CA0: The interrupting rating drops as line voltage rises: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 9 kA at 690 V. For most 400 V-class industrial panels the 187 kA rating gives substantial headroom above typical 50–65 kA SCCR requirements. The 630 A rating holds only at 40 °C ambient inside the enclosure. Above that, continuous current must be reduced: 612 A at 45 °C, 593 A at 50 °C, 575 A at 55 °C, 557 A at 60 °C, 538 A at 65 °C, and 520 A at 70 °C. If your panel ambient runs 50 °C, you lose roughly 6 % of the headline rating. No auxiliary switch is included (specified as 'without'), so if you need status feedback, order the auxiliary switch block separately.","metaTitle":"Siemens 3VA2463-6HL32-0CA0 SENTRON MCCB, 630 A, 3-Pole, 242","metaDescription":"Siemens SENTRON 3VA2463-6HL32-0CA0 molded case circuit breaker, 630 A continuous at 40 °C, 3-pole, 242 kA breaking at 240 V. Current lifecycle stage. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"5 670 A","Minimum":"945 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"9 kA","at 40 °C":"630 A","at 45 °C":"612 A","at 50 °C":"593 A","at 55 °C":"575 A","at 60 °C":"557 A","at 65 °C":"538 A","at 70 °C":"520 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"164.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2463-6HL32-0AA0","Design Of The Auxiliary Switch":"Without","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"630 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"630 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ff193dd53a0856db1ca969741fab18b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=103150&mlfb=3VA2463-6HL32-0CA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2463-6HL32-0CA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2463-6HL32-0CA0 and how is it quoted?","answer":"It is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — stock and lead time are confirmed at quote time."},{"question":"What is the breaking capacity of this MCCB at 415 V?","answer":"The breaking capacity is 187 kA at 415 V, matching the rating at 440 V."},{"question":"Does this breaker include an undervoltage release?","answer":"Yes, it has a built-in undervoltage release (UVR) as the auxiliary release. No separate undervoltage module is required."},{"question":"What are the physical dimensions of 3VA2463-6HL32-0CA0?","answer":"Height 248 mm, width 138 mm, depth 110 mm. The 138 mm width fits three 45 mm pole spaces on a DIN rail."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2463-6HL32-0CA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2463-6HL32-0CA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}