{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2463-6HN32-0AJ0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2463-6HN32-0AJ0","canonicalUrl":"https://aoctrl.com/siemens/3VA2463-6HN32-0AJ0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2463-6HN32-0AJ0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, Molded case circuit breaker 3VA2463-6HN32-0AJ0, 3-pole, 630 A rated current at 40 °C, 242 kA breaking capacity at 240 V, ETU350 electronic trip unit, line protection.","salesMarkdown":"The Siemens SENTRON 3VA2463-6HN32-0AJ0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current of 630 A at 40 °C and a breaking capacity of 242 kA at 240 V. ## Breaking capacity across voltage This MCCB's interrupting rating drops as voltage rises: 242 kA at 240 V, 187 kA at both 415 V and 440 V, 121 kA at 500 V, and 40 kA at 690 V (–). That 40 kA at 690 V is still a serious number — it's not a derated afterthought. If your panel feeds a 690 V drive or a step-up transformer secondary, this breaker handles the fault without upstream coordination headaches. Rated 630 A at 40 °C ambient, the 3VA2463-6HN32-0AJ0 derates to 520 A at 70 °C (–). That 110 mm depth fits standard MCCB mounting plates and most 800 mm deep enclosures without protruding past the gland plate. ## What the ETU350 gives you Compared to a thermal-magnetic breaker, the ETU350 lets you set the short-time delay to coordinate with downstream breakers without sacrificing the instantaneous trip for high faults. That's useful for selective coordination in a distribution panel where you want the feeder to hold for a downstream fault but clear its own bus fault instantly. The trip indicator confirms the breaker opened on a fault, not manually — helpful for fault diagnosis on a remote or automated line. ## Sourcing and ordering The order code 3VA2463-6HN32-0AJ0 is the full factory configuration — no field-installable auxiliaries or shunt trips to add later, so verify your auxiliary contact count and undervoltage release requirement before you commit the BOM line.","metaTitle":"Siemens 3VA2463-6HN32-0AJ0 SENTRON MCCB, 630A, 242kA","metaDescription":"Siemens SENTRON 3VA2463-6HN32-0AJ0 molded case circuit breaker, 630A rated current, 242kA breaking capacity at 240V, ETU350 trip unit, 3-pole, line protection. Current production,","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"40 kA","at 40 °C":"630 A","at 45 °C":"612 A","at 50 °C":"593 A","at 55 °C":"575 A","at 60 °C":"557 A","at 65 °C":"538 A","at 70 °C":"520 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"162 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HP","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"630 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2463-6HN32-0AA0","Design of the auxiliary release":"Without auxiliary release","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"12","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"630 A","Adjustable response value current / li max.":"5 670 A","Adjustable response value current / li min.":"5 670 A","Adjustable response value current / lr min.":"250 A","Adjustable response value current / Isd max.":"0 A","Adjustable response value current / Isd min.":"0 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB11","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"630 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"35 x 10","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ff193dd53a0856db1ca969741fab18b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=406263&mlfb=3VA2463-6HN32-0AJ0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2463-6HN32-0AJ0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2463-6HN32-0AJ0 at 415 V?","answer":"187 kA at 415 V. The full voltage curve is 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 40 kA at 690 V."},{"question":"What trip unit does this MCCB use?","answer":"The ETU350 electronic trip unit with adjustable long-time, short-time, instantaneous, and ground-fault protection."},{"question":"Where can I buy 3VA2463-6HN32-0AJ0 and get current pricing?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2463-6HN32-0AJ0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2463-6HN32-0AJ0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}