{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2463-6JP32-0AE0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2463-6JP32-0AE0","canonicalUrl":"https://aoctrl.com/siemens/3VA2463-6JP32-0AE0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2463-6JP32-0AE0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, molded case circuit breaker (MCCB), 3-pole, 630 A rated continuous current, line protection design, with communication function.","salesMarkdown":"The interrupting capacity varies by system voltage: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 9 kA at 690 V — these are the fault currents the breaker can safely clear without damage to upstream gear. The minimum short-circuit breaking capacity is 945 A, and the maximum is 5 670 A, which sets the range of fault currents the internal trip unit responds to. The continuous current rating is temperature-dependent: at 40 °C it carries the full 630 A; at 50 °C it derates to 570 A; at 60 °C to 510 A; and at 70 °C to 450 A. Maximum power dissipation is 162 W, which factors into enclosure thermal calculations. The breaker measures 138 mm wide by 248 mm tall by 110 mm deep. The communication function is built in, meaning it can report status and trip events over the SENTRON bus system — no separate add-on module required for basic telemetry.","metaTitle":"Siemens 3VA2463-6JP32-0AE0 SENTRON MCCB, 630 A, 3-Pole","metaDescription":"Siemens 3VA2463-6JP32-0AE0 SENTRON molded case circuit breaker, 630 A continuous, 3-pole, line protection. Interrupting ratings up to 242 kA at 240 V. Current lifecycle stage. Quot","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"5 670 A","Minimum":"945 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"9 kA","at 40 °C":"630 A","at 45 °C":"600 A","at 50 °C":"570 A","at 55 °C":"540 A","at 60 °C":"510 A","at 65 °C":"480 A","at 70 °C":"450 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"162 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2463-6JP32-0AA0","Design Of The Auxiliary Switch":"4 auxiliary switches HQ","Design Of The Auxiliary Release":"Without auxiliary release","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"630 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"630 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ff193dd53a0856db1ca969741fab18b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=399916&mlfb=3VA2463-6JP32-0AE0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2463-6JP32-0AE0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of 3VA2463-6JP32-0AE0 at 415 V?","answer":"At 415 V the interrupting rating is 187 kA. At 240 V it is 242 kA, at 500 V it is 121 kA, and at 690 V it is 9 kA."},{"question":"Where can I buy 3VA2463-6JP32-0AE0?","answer":"This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2463-6JP32-0AE0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2463-6JP32-0AE0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}