{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2463-6JP32-0AL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2463-6JP32-0AL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2463-6JP32-0AL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2463-6JP32-0AL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA2 IEC frame 630, 3-pole circuit breaker, breaking capacity class H, Icu=85kA @ 415V, ETU550 LSI trip unit, In=630A, with 2 auxiliary switch changeover H and 1 trip alarm switch changeover.","salesMarkdown":"## What this 3VA2 breaker delivers The Siemens 3VA2463-6JP32-0AL0 is a 3-pole IEC frame 630 circuit breaker with a class H breaking capacity — Icu of 85 kA at 415 V. The ETU550 trip unit provides LSI protection: long-time (Ir adjustable 250 A to 630 A), short-time (Isd 0.6 to 9× In), and instantaneous (Ii 1.5 to 9× In). This selectivity profile suits it for main or tie breaker duty in a distribution board where you need to coordinate with downstream feeders. The breaker ships with two auxiliary switch changeover contacts (H type) and one trip alarm switch changeover contact already fitted. The neutral conductor protection option requires an external current transformer, which is not in the box.","metaTitle":"Siemens 3VA2463-6JP32-0AL0 Circuit Breaker, 630A, 85kA @ 415","metaDescription":"Siemens 3VA2463-6JP32-0AL0 IEC frame 630 circuit breaker, 3-pole, ETU550 LSI, 630A, Icu=85kA @ 415V. Current lifecycle stage. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ff193dd53a0856db1ca969741fab18b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1513764&mlfb=3VA2463-6JP32-0AL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2463-6JP32-0AL0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this breaker?","answer":"The Icu is 85 kA at 415 V, which is the class H rating for the 3VA2 IEC frame 630. This is the maximum short-circuit current the breaker can safely interrupt."},{"question":"What trip unit and protection functions does it have?","answer":"It uses an ETU550 electronic trip unit with LSI protection: long-time pickup Ir adjustable 250 A to 630 A, short-time pickup Isd 0.6 to 9× In, and instantaneous pickup Ii 1.5 to 9× In."},{"question":"Where can I buy 3VA2463-6JP32-0AL0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2463-6JP32-0AL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2463-6JP32-0AL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}