{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2463-6JP32-0CC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2463-6JP32-0CC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2463-6JP32-0CC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2463-6JP32-0CC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2463-6JP32-0CC0, molded case circuit breaker, 3-pole, 630 A continuous, line protection, with undervoltage release and communication function.","salesMarkdown":"The continuous current derates as ambient rises: 600 A at 45 °C, 570 A at 50 °C, 540 A at 55 °C, 510 A at 60 °C, 480 A at 65 °C, and 450 A at 70 °C — so the real-world ampacity depends on your panel's internal temperature, not just the nameplate 630 A. Breaking capacity is where this frame earns its keep: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 9 kA at 690 V. The adjustable trip unit spans a minimum of 945 A to a maximum of 5 670 A, giving you the range to tune the magnetic pickup to the downstream load's inrush profile. The breaker includes a communication function, meaning it can report status and trip events over a bus — useful for a BMS or SCADA system that needs to know which feeder opened without a physical walk-down. The basic switch variant is 3VA2463-6JP32-0AA0 — the -0CC0 suffix adds the communication module and the UVR. If your BOM was written around the -0AA0, the -0CC0 drops into the same physical cutout and bus connection; the only difference is the control wiring for the UVR and the comms cable. Maximum power loss is 164.5 W at rated load — factor that into your panel's thermal budget.","metaTitle":"Siemens 3VA2463-6JP32-0CC0 SENTRON MCCB, 630 A, 3-pole","metaDescription":"Siemens SENTRON 3VA2463-6JP32-0CC0 molded case circuit breaker, 630 A continuous, 3-pole, 242 kA at 240 V. Active production. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"5 670 A","Minimum":"945 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"9 kA","at 40 °C":"630 A","at 45 °C":"600 A","at 50 °C":"570 A","at 55 °C":"540 A","at 60 °C":"510 A","at 65 °C":"480 A","at 70 °C":"450 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"164.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2463-6JP32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"630 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"630 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ff193dd53a0856db1ca969741fab18b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=15548&mlfb=3VA2463-6JP32-0CC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2463-6JP32-0CC0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2463-6JP32-0CC0 at 415 V?","answer":"The breaking capacity is 187 kA at 415 V, and the same at 440 V. At 240 V it reaches 242 kA."},{"question":"Where can I buy 3VA2463-6JP32-0CC0 and how is it quoted?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"Does 3VA2463-6JP32-0CC0 include an undervoltage release?","answer":"Yes, it is factory-fitted with an undervoltage release (UVR) and also includes two auxiliary switches (HQ type) and a communication function."},{"question":"What are the mounting dimensions of this MCCB?","answer":"The breaker measures 138 mm wide, 248 mm tall, and 110 mm deep. It fits a standard 3-pole MCCB bucket or DIN-rail adapter."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2463-6JP32-0CC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2463-6JP32-0CC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}