{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2463-6JP32-0KA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2463-6JP32-0KA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2463-6JP32-0KA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2463-6JP32-0KA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2463-6JP32-0KA0, molded case circuit breaker, 3-pole, 630 A rated, line protection, shunt trip release, 242 kA interrupting at 240 V.","salesMarkdown":"## Interrupting capacity and thermal derating — the real fit numbers Interrupting capacity is voltage-dependent: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 9 kA at 690 V. The continuous current rating of 630 A is at 40 °C; derate linearly to 450 A at 70 °C. For a panel running at 50 °C ambient, the usable current drops to 570 A. The shunt trip release allows remote tripping from a control system or emergency-stop circuit.","metaTitle":"Siemens 3VA2463-6JP32-0KA0 SENTRON MCCB, 630 A, 3-Pole, Shun","metaDescription":"Siemens SENTRON 3VA2463-6JP32-0KA0 molded case circuit breaker, 630 A rated, 3-pole, line protection, shunt trip release, 242 kA at 240 V. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"5 670 A","Minimum":"945 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"9 kA","at 40 °C":"630 A","at 45 °C":"600 A","at 50 °C":"570 A","at 55 °C":"540 A","at 60 °C":"510 A","at 65 °C":"480 A","at 70 °C":"450 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"162 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2463-6JP32-0AA0","Design Of The Auxiliary Switch":"Without","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"630 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"630 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ff193dd53a0856db1ca969741fab18b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=313287&mlfb=3VA2463-6JP32-0KA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2463-6JP32-0KA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2463-6JP32-0KA0 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability — no stock count or price is published here."},{"question":"What is the closest functional second-source to 3VA2463-6JP32-0KA0?","answer":"The closest peer in the SENTRON family is the 3VA2116-5JP32-0AE0, but it is a lower-current frame (160 A class) and does not match the 630 A rating or the interrupting capacity of this breaker. For a true form-fit-function alternate at 630 A, no direct second-source is listed — the 3VA2463-6JP32-0KA0 is the current production variant."},{"question":"What is the depth of 3VA2463-6JP32-0KA0?","answer":"The depth is 110 mm (4.33 in)."},{"question":"What is the width of 3VA2463-6JP32-0KA0?","answer":"The width is 138 mm (5.43 in)."},{"question":"Will 3VA2463-6JP32-0KA0 drop into a panel specified around 3VA2116-5JP32-0AE0 without rewiring?","answer":"No — the 3VA2116-5JP32-0AE0 is a 160 A frame; the 3VA2463-6JP32-0KA0 is a 630 A frame with different dimensions and bus-bar spacing. Panel cutouts and bus connections would need to be reworked."},{"question":"What compliance documentation does Siemens provide for 3VA2463-6JP32-0KA0?","answer":"The evidence does not list specific compliance certificates (RoHS, REACH, UL, IEC) for this order code. Standard Siemens SENTRON MCCBs typically carry UL 489, IEC 60947-2, and CE marking — confirm the exact documentation with your RFQ request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2463-6JP32-0KA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2463-6JP32-0KA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}