{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2463-6KP32-0HH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2463-6KP32-0HH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2463-6KP32-0HH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2463-6KP32-0HH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2463-6KP32-0HH0, molded case circuit breaker, 3-pole, 630 A, ETU850 electronic trip unit, line protection, 242 kA at 240 V, 187 kA at 415 V.","salesMarkdown":"The Siemens 3VA2463-6KP32-0HH0 is a 3-pole SENTRON molded case circuit breaker rated for 630 A continuous current at 40 °C, with an ETU850 electronic trip unit. The 630 A figure is the maximum uninterrupted current the breaker can carry under the listed conditions — above that, the trip unit initiates a protective opening. Breaking capacity is the other headline: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 40 kA at 690 V. The front panel carries IP40 protection. ## Temperature derating — the curve that governs real-world current The 630 A rating is valid at 40 °C ambient. Above that, the breaker must be derated: 600 A at 45 °C, 570 A at 50 °C, 540 A at 55 °C, 510 A at 60 °C, 480 A at 65 °C, and 450 A at 70 °C. If your panel ambient runs at 50 °C, the usable continuous current drops to 570 A — a 9.5 % reduction. Physical footprint: 248 mm height, 138 mm width, 110 mm depth. The 138 mm width is the 3-pole frame width — verify the mounting cutout in your switchgear matches. The 110 mm depth includes the rear arc chamber and terminal extensions; ensure clearance behind the mounting plate for cable lugs and bus connections. Maximum power loss is 162 W at rated current. That heat must be dissipated inside the enclosure — factor it into your panel cooling calculation, especially if the breaker is grouped with other high-current devices in a sealed cabinet.","metaTitle":"Siemens 3VA2463-6KP32-0HH0 SENTRON MCCB, 630A, 3-Pole, ETU85","metaDescription":"Siemens SENTRON 3VA2463-6KP32-0HH0 molded case circuit breaker, 630A rated continuous current, 3-pole, ETU850 electronic trip unit, 242kA at 240V. Active production, sourced to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"40 kA","at 40 °C":"630 A","at 45 °C":"600 A","at 50 °C":"570 A","at 55 °C":"540 A","at 60 °C":"510 A","at 65 °C":"480 A","at 70 °C":"450 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"Yes","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"162 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Rated continuous current Iu":"630 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2463-6KP32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL30","Design of the overcurrent release":"ETU850","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"12","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / lg min.":"5 670 A","Adjustable response value current / li max.":"5 670 A","Adjustable response value current / li min.":"945 A","Neutral conductors / upgradeable/retrofittable":"Yes","Number of CO contacts / for auxiliary contacts":"3","Protection Function Of The Overcurrent Release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"630 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Mechanical service life (switching cycles) / typical":"15 000","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"35 x 10","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ff193dd53a0856db1ca969741fab18b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=494821&mlfb=3VA2463-6KP32-0HH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2463-6KP32-0HH0/alternatives.json"},"ai":{"faq":[{"question":"What trip unit does this breaker use?","answer":"It uses the ETU850 electronic trip unit, which provides adjustable long-time, short-time, instantaneous, and ground-fault protection curves for selective coordination."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2463-6KP32-0HH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2463-6KP32-0HH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}