{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2463-6KP32-0KA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2463-6KP32-0KA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2463-6KP32-0KA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2463-6KP32-0KA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2463-6KP32-0KA0, molded case circuit breaker, 3-pole, 630 A rated continuous current at 40 °C, breaking capacity 242 kA at 240 V AC.","salesMarkdown":"The ETU850 electronic trip unit provides adjustable protection curves, and the shunt trip (STL) release allows remote tripping — a safety requirement for emergency-stop circuits. No ground-fault monitoring or auxiliary contacts on this variant, so plan those externally if the application needs them. The 630 A rating holds only at 40 °C ambient. Above that, derate: 600 A at 45 °C, 570 A at 50 °C, 540 A at 55 °C, 510 A at 60 °C, 480 A at 65 °C, and 450 A at 70 °C (–). If the panel ambient runs 50 °C, the breaker's usable current drops to 570 A — size the upstream transformer and bus accordingly. That 110 mm depth matters for enclosure depth — standard 200 mm deep enclosures have clearance for wiring and the shunt trip wiring tray. Width of 138 mm determines the DIN-rail or mounting-plate spacing; allow at least 150 mm per breaker for adjacent units and cable bending radius.","metaTitle":"Siemens 3VA2463-6KP32-0KA0 SENTRON MCCB, 630 A, 242 kA at 24","metaDescription":"Siemens SENTRON 3VA2463-6KP32-0KA0 molded case circuit breaker, 630 A rated current, 242 kA breaking at 240 V. Active production. Quoted to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"40 kA","at 40 °C":"630 A","at 45 °C":"600 A","at 50 °C":"570 A","at 55 °C":"540 A","at 60 °C":"510 A","at 65 °C":"480 A","at 70 °C":"450 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"Yes","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"162 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Rated continuous current Iu":"630 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2463-6KP32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL33","Design of the overcurrent release":"ETU850","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"12","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"630 A","Adjustable response value current / li max.":"5 670 A","Adjustable response value current / li min.":"945 A","Adjustable response value current / lr min.":"252 A","Adjustable response value current / Isd max.":"5 670 A","Adjustable response value current / Isd min.":"378 A","Neutral conductors / upgradeable/retrofittable":"Yes","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"630 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"35 x 10","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ff193dd53a0856db1ca969741fab18b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=314750&mlfb=3VA2463-6KP32-0KA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2463-6KP32-0KA0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2463-6KP32-0KA0 at 415 V?","answer":"187 kA at 415 V. The same rating applies at 440 V."},{"question":"Where can I buy 3VA2463-6KP32-0KA0?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment."},{"question":"Does 3VA2463-6KP32-0KA0 include a shunt trip or undervoltage release?","answer":"It includes a shunt trip (STL) release for remote tripping. No undervoltage release is fitted."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2463-6KP32-0KA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2463-6KP32-0KA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}