{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2463-6KP32-0KC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2463-6KP32-0KC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2463-6KP32-0KC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2463-6KP32-0KC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2463-6KP32-0KC0, molded case circuit breaker, 3-pole, 630 A continuous, line protection design, with communication function and shunt trip.","salesMarkdown":"The basic switch variant is order code 3VA2463-6KP32-0AA0. ## Rating depth: current, temperature, and breaking capacity The continuous current rating of 630 A is at 40 °C ambient. Derate linearly through the table: 600 A at 45 °C, 570 A at 50 °C, down to 450 A at 70 °C. For a panel running hot — say 50 °C ambient — plan for 570 A continuous, not the full 630 A. Breaking capacity drops with system voltage: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 9 kA at 690 V. For a 415 V industrial feeder, the 187 kA rating gives substantial headroom over typical available fault current. The adjustable thermal-magnetic trip range spans 945 A minimum to 5 670 A maximum, giving flexibility to coordinate with downstream breakers. Maximum power loss is 162 W — factor that into enclosure ventilation. The 110 mm depth (4.33 in) includes the breaker body; add clearance for the shunt trip wiring and auxiliary switch connections. ## Built-in communication and auxiliary functions The communication function enables remote monitoring and control — useful for a facility moving toward smart distribution or needing breaker status in a SCADA system.","metaTitle":"Siemens SENTRON 3VA2463-6KP32-0KC0 MCCB, 630 A, 3-Pole","metaDescription":"Siemens SENTRON 3VA2463-6KP32-0KC0 molded case circuit breaker, 630 A continuous, 3-pole, line protection with communication. Breaking capacity 242 kA at 240 V. Current production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"5 670 A","Minimum":"945 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"9 kA","at 40 °C":"630 A","at 45 °C":"600 A","at 50 °C":"570 A","at 55 °C":"540 A","at 60 °C":"510 A","at 65 °C":"480 A","at 70 °C":"450 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"162 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Of The Supplied Basic Switch":"3VA2463-6KP32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"630 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"630 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ff193dd53a0856db1ca969741fab18b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=383113&mlfb=3VA2463-6KP32-0KC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2463-6KP32-0KC0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2463-6KP32-0KC0?","answer":"Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels. No stock count or price figure is published here."},{"question":"What is the breaking capacity of 3VA2463-6KP32-0KC0 at 415 V?","answer":"187 kA at 415 V, which is the same rating as at 440 V. At 240 V it reaches 242 kA; at 500 V it drops to 121 kA; at 690 V it is 9 kA."},{"question":"Does 3VA2463-6KP32-0KC0 have communication capability?","answer":"Yes, the communication function is built in, enabling remote monitoring and integration into a smart distribution or SCADA system."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2463-6KP32-0KC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2463-6KP32-0KC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}