{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2463-7HL32-0HC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2463-7HL32-0HC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2463-7HL32-0HC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2463-7HL32-0HC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON molded case circuit breaker, 3VA2463-7HL32-0HC0, 3-pole, 630 A continuous at 40 °C, line protection, with shunt trip and 2 auxiliary switches HQ.","salesMarkdown":"## SENTRON 3VA2 MCCB, 630 A Frame — Line Protection with Shunt Trip It carries a fixed thermal-magnetic trip unit with a minimum trip setting of 945 A and maximum 5 670 A — the adjustable long-time and short-time pickup bands cover motor and feeder protection curves without a separate relay. Breaking capacity is 330 kA at 240 V AC, 242 kA at 415/440 V, 187 kA at 500 V, and 9 kA at 690 V. The frame holds up to 162 W power loss at full load, so panel ventilation matters when grouping multiple breakers. ## Dimensions, Mounting, and Ambient Derating Footprint: 138 mm wide × 248 mm tall × 110 mm deep. Continuous current derates linearly from 630 A at 40 °C to 520 A at 70 °C. At 50 °C it's still good for 593 A; at 60 °C, 557 A.","metaTitle":"Siemens 3VA2463-7HL32-0HC0 SENTRON MCCB, 630A, 3-Pole","metaDescription":"Siemens SENTRON 3VA2463-7HL32-0HC0 molded case circuit breaker, 630A at 40°C, 3-pole, line protection. Breaking capacity 330kA at 240V. Current lifecycle stage. Quoted to order aga","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"5 670 A","Minimum":"945 A","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"9 kA","at 40 °C":"630 A","at 45 °C":"612 A","at 50 °C":"593 A","at 55 °C":"575 A","at 60 °C":"557 A","at 65 °C":"538 A","at 70 °C":"520 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"162 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2463-7HL32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"630 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"630 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ff193dd53a0856db1ca969741fab18b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=293635&mlfb=3VA2463-7HL32-0HC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2463-7HL32-0HC0/alternatives.json"},"ai":{"faq":[{"question":"Does this breaker include a shunt trip or auxiliary contacts?","answer":"Yes. It ships with a factory-installed shunt trip (STL) release for remote tripping and two HQ auxiliary switches for status feedback. No undervoltage release or ground-fault monitoring."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2463-7HL32-0HC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2463-7HL32-0HC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}