{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2463-7HN32-0CC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2463-7HN32-0CC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2463-7HN32-0CC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2463-7HN32-0CC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2463-7HN32-0CC0, molded case circuit breaker, 3-pole, line protection, 630 A at 40 °C, 330 kA at 240 V, ETU350 release, undervoltage release.","salesMarkdown":"It carries a 330 kA breaking capacity at 240 V, stepping down to 242 kA at 415 V and 440 V, 187 kA at 500 V, and 52.5 kA at 690 V — the full fault-interruption curve for a high-capacity distribution main. The 630 A rating at 40 °C derates with ambient temperature: 612 A at 45 °C, 593 A at 50 °C, 575 A at 55 °C, 557 A at 60 °C, 538 A at 65 °C, 520 A at 70 °C. This MCCB uses an ETU350 electronic trip unit. ## Panel integration The breaker measures 138 mm wide, 248 mm high, and 110 mm deep — a standard SENTRON 3VA2 frame footprint for 630 A class. ## Operating conditions Maximum power loss is 164.5 W — account for heat dissipation in the enclosure sizing. Mechanical endurance is 15,000 operations. No communication function, phase failure detection, or ground fault monitoring is built in — the ETU350 handles overcurrent protection only.","metaTitle":"Siemens 3VA2463-7HN32-0CC0 SENTRON MCCB, 630 A, 330 kA","metaDescription":"Siemens 3VA2463-7HN32-0CC0 SENTRON molded case circuit breaker, 630 A rated at 40 °C, 330 kA breaking at 240 V. ETU350 release, UVR. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"52.5 kA","at 40 °C":"630 A","at 45 °C":"612 A","at 50 °C":"593 A","at 55 °C":"575 A","at 60 °C":"557 A","at 65 °C":"538 A","at 70 °C":"520 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"164.5 W","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"630 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2463-7HN32-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB24","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"12","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"630 A","Adjustable response value current / li max.":"5 670 A","Adjustable response value current / li min.":"5 670 A","Adjustable response value current / lr min.":"250 A","Adjustable response value current / Isd max.":"0 A","Adjustable response value current / Isd min.":"0 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"C","Max. rated operational current of the frame size":"630 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"35 x 10","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ff193dd53a0856db1ca969741fab18b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=146354&mlfb=3VA2463-7HN32-0CC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2463-7HN32-0CC0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2463-7HN32-0CC0 at different voltages?","answer":"330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 52.5 kA at 690 V."},{"question":"What trip unit and releases does this MCCB use?","answer":"It uses an ETU350 electronic overcurrent release, includes an undervoltage release (UVR), and has two HQ auxiliary switches. The basic switch assembly is 3VA2463-7HN32-0AA0; the integrated auxiliary trip is 3VA9608-0BB24."},{"question":"How do I get pricing and availability for 3VA2463-7HN32-0CC0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability confirmation — stock levels and lead times are verified at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2463-7HN32-0CC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2463-7HN32-0CC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}