{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2463-8JP32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2463-8JP32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2463-8JP32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2463-8JP32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2463-8JP32-0AA0, 3-pole molded case circuit breaker, 630 A at 40 °C, ETU550 electronic trip unit, 440 kA interrupting at 240 V, line protection design.","salesMarkdown":"The Siemens SENTRON 3VA2463-8JP32-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying 630 A continuous at 40 °C with an ETU550 electronic trip unit. Interrupting ratings climb to 440 kA at 240 V, 330 kA at 415 V, and 220 kA at 500 V — numbers that give you serious fault-current headroom for a 480 V or 400 V industrial service. That selectivity matters when a fault on a branch shouldn't black out the whole line. If the panel runs hotter — and a packed enclosure with a 630 A breaker usually does — you need to derate: 600 A at 45 °C, 570 A at 50 °C, all the way down to 450 A at 70 °C.","metaTitle":"Siemens 3VA2463-8JP32-0AA0 SENTRON MCCB, 630 A, ETU550, 440","metaDescription":"Siemens SENTRON 3VA2463-8JP32-0AA0 molded case circuit breaker, 630 A at 40 °C, ETU550 electronic trip, 440 kA at 240 V. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"5 670 A","Minimum":"945 A","at 240 V":"440 kA","at 415 V":"330 kA","at 440 V":"330 kA","at 500 V":"220 kA","at 690 V":"52.5 kA","at 40 °C":"630 A","at 45 °C":"600 A","at 50 °C":"570 A","at 55 °C":"540 A","at 60 °C":"510 A","at 65 °C":"480 A","at 70 °C":"450 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"162 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"630 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"630 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"L","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ff193dd53a0856db1ca969741fab18b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=191182&mlfb=3VA2463-8JP32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2463-8JP32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is 3VA2463-8JP32-0AA0's listed depth?","answer":"The depth is 110 mm (4.33 in)."},{"question":"What is 3VA2463-8JP32-0AA0's listed width?","answer":"The width is 138 mm (5.43 in)."},{"question":"What compliance documentation does this brand provide for 3VA2463-8JP32-0AA0?","answer":"Standard Siemens documentation for the SENTRON line includes RoHS, REACH, UL, and IEC compliance declarations. These are available through the manufacturer's support portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2463-8JP32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2463-8JP32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}