{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2510-5HL32-0BC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2510-5HL32-0BC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2510-5HL32-0BC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2510-5HL32-0BC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, molded case circuit breaker, 3VA2510-5HL32-0BC0, 3-pole, 1000 A, ETU320 trip unit, 187 kA at 240 V, 121 kA at 415 V.","salesMarkdown":"The interrupting ratings are the headline: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 52.5 kA at 690 V. The ETU320 trip unit gives you adjustable long-time, short-time, and instantaneous protection curves, plus an undervoltage release is fitted as standard. No trip indicator on the front, so fault diagnostics rely on the release's own flag or a connected indication. At 60 °C it derates to 955 A, at 65 °C to 885 A, and at 70 °C to 815 A. Physical footprint: 210 mm wide, 320 mm tall, 120 mm deep. That's a 3-pole frame in the 3VA2 platform — it bolts into a standard MCCB mounting pattern, not a DIN rail.","metaTitle":"Siemens 3VA2510-5HL32-0BC0 SENTRON MCCB, 1000 A, 187 kA at 2","metaDescription":"Siemens 3VA2510-5HL32-0BC0 SENTRON molded case circuit breaker, 3-pole, 1000 A, ETU320, 187 kA at 240 V. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"120 mm","Width":"210 mm","Height":"320 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"52.5 kA","at 40 °C":"1 000 A","at 45 °C":"1 000 A","at 50 °C":"1 000 A","at 55 °C":"1 000 A","at 60 °C":"955 A","at 65 °C":"885 A","at 70 °C":"815 A","Depth [In]":"4.72 in","Width [In]":"8.27 in","Height [In]":"12.6 in","Trip Indicator":"No","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"332.5 W","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"#BEZUG!","Courant permanent assigné Iu":"1 000 A","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB11","Product Extension / Optional / Motor Drive":"No","Adjustable response value current / li max.":"10 000 A","Adjustable response value current / li min.":"1 500 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Max. rated operational current of the frame size":"1 000 A","Mechanical Service Life (Switching Cycles) / Typical":"10 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"50 x 28 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 4 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=660258&mlfb=3VA2510-5HL32-0BC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2510-5HL32-0BC0/alternatives.json"},"ai":{"faq":[{"question":"Does this breaker have a trip indicator or communication capability?","answer":"No trip indicator on the front, and no communication function. It does have an undervoltage release and two auxiliary switches (HQ type) for status feedback."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2510-5HL32-0BC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2510-5HL32-0BC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}