{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2510-5HL32-0HL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2510-5HL32-0HL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2510-5HL32-0HL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2510-5HL32-0HL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2510-5HL32-0HL0, molded case circuit breaker, 3-pole, rated continuous current 1000 A, ETU320 electronic trip unit, breaking capacity 187 kA at 240 V.","salesMarkdown":"It's built for line protection in distribution panels, sized to handle high-fault currents: 187 kA at 240 V, 121 kA at 415 V, and 53 kA at 690 V. The 320 mm height, 210 mm width, and 120 mm depth mean it fits standard MCCB mounting footprints — check the back-panel cutout against your existing switchgear before committing the BOM line. Full 1000 A is available up to 55 °C ambient. Above that, the continuous rating drops: 955 A at 60 °C, 885 A at 65 °C, 815 A at 70 °C. ## Trip unit and adjustments The ETU320 release gives you adjustable Ir (400–1000 A) and Ii (1500–10000 A), plus a configurable time delay tr (0.5–17 s). That means you can tune the short-time pickup and delay to coordinate with downstream breakers — useful for selective coordination studies.","metaTitle":"Siemens SENTRON 3VA2510-5HL32-0HL0 MCCB, 1000 A, 3-pole","metaDescription":"Siemens SENTRON 3VA2510-5HL32-0HL0 molded case circuit breaker, 1000 A rated continuous current, 3-pole, ETU320 release. Breaking capacity 187 kA at 240 V, 121 kA at 415 V, 53 kA a","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"120 mm","Width":"210 mm","title":"3VA2510-5HL32-0HL0","Height":"320 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 690 V":"53 kA","at 40 °C":"1 000 A","at 45 °C":"1 000 A","at 50 °C":"1 000 A","at 55 °C":"1 000 A","at 60 °C":"955 A","at 65 °C":"885 A","at 70 °C":"815 A","Width [in]":"8.3 in","Height [in]":"12.6 in","description":"circuit breaker 3VA2 IEC frame 1000 breaking capacity class M Icu=55kA @ 415V 3-pole, line protection ETU320, LI, In=1000A overload protection Ir=400A...1000A short-circuit protection Ii=1.5...10 x In nut keeper kit shunt trip (STL) 12-30V DC, 24V AC 50/60Hz 2 auxiliary switches HQ 1 trip alarm switch HQ 1 electrical alarm switch","Number of poles":"3","Product version":"Line protection","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"10 000","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"123 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"1 000 A","Rated insulation voltage Ui":"800 V","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value current / Ir max.":"1 000 A","Adjustable response value current / li max.":"10 000 A","Adjustable response value current / li min.":"1 500 A","Adjustable response value current / lr min.":"400 A","Neutral conductors / upgradeable/retrofittable":"No","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"1 000 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 4"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/59938b76169cd9a58de5eac25d6174b2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=660272&mlfb=3VA2510-5HL32-0HL0"},"ai":{"faq":[{"question":"What is the breaking capacity of this MCCB at different voltages?","answer":"At 240 V it's rated 187 kA, at 415 V it's 121 kA, and at 690 V it's 53 kA. These are the interrupting ratings for the 3-pole unit."},{"question":"Where can I buy 3VA2510-5HL32-0HL0 and how is it quoted?","answer":"We source this part to order against an RFQ. Submit a request with your target quantity and delivery window; we'll confirm availability and current pricing at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2510-5HL32-0HL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2510-5HL32-0HL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}