{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2510-5HL32-0KK0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2510-5HL32-0KK0","canonicalUrl":"https://aoctrl.com/siemens/3VA2510-5HL32-0KK0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2510-5HL32-0KK0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA2 IEC frame 1000 circuit breaker, 3-pole, 1000A, Icu=55kA @ 415V, ETU320 LI trip unit, shunt trip left 208-277V AC, 1 auxiliary switch, nut keeper kit.","salesMarkdown":"The Siemens 3VA2510-5HL32-0KK0 is a 3VA2 IEC frame 1000 molded-case circuit breaker rated 1000 A continuous, with a breaking capacity class M achieving Icu=55 kA at 415 V AC. The ETU320 electronic trip unit provides LI (long-time and instantaneous) protection, with overload pickup Ir adjustable from 400 A to 1000 A and short-circuit pickup Ii adjustable from 1.5 to 10 x In. This adjustability lets you coordinate the breaker downstream without swapping trip units. The shunt trip allows remote tripping from a safety circuit or emergency-stop chain — common in conveyor, pump, or compressor panels where a PLC or E-stop button must kill the main breaker.","metaTitle":"Siemens 3VA2510-5HL32-0KK0 Circuit Breaker, 1000A, 55kA @ 41","metaDescription":"Siemens 3VA2510-5HL32-0KK0 3VA2 IEC frame 1000 circuit breaker, 1000A, Icu=55kA @ 415V, ETU320 LI, shunt trip, aux switch. Current production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1437127&mlfb=3VA2510-5HL32-0KK0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2510-5HL32-0KK0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2510-5HL32-0KK0 and get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time."},{"question":"What does the Icu=55kA @ 415V rating mean for my installation?","answer":"The 55 kA interrupting capacity at 415 V AC means this breaker can safely clear a fault current up to that magnitude without catastrophic failure. It is sized for main or feeder positions in industrial switchboards where the available fault current is high — typical for transformer-fed 400 V distribution."},{"question":"What accessories are included with this breaker?","answer":"The 3VA2510-5HL32-0KK0 includes a left-side shunt trip (208-277 V AC / 220-250 V DC), one auxiliary switch, and a nut keeper kit to secure terminal hardware against vibration."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2510-5HL32-0KK0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2510-5HL32-0KK0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}