{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2510-5HN32-0AD0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2510-5HN32-0AD0","canonicalUrl":"https://aoctrl.com/siemens/3VA2510-5HN32-0AD0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2510-5HN32-0AD0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2, molded case circuit breaker, 3-pole, 1000 A, 187 kA at 240 V, ETU350 electronic trip unit, line protection version.","salesMarkdown":"The Siemens 3VA2510-5HN32-0AD0 is a SENTRON 3VA2 molded case circuit breaker in the line protection version, rated 1000 A continuous current (Iu) across 40 °C to 55 °C ambient, derating to 955 A at 60 °C and 815 A at 70 °C. Breaking capacity runs 187 kA at 240 V, 121 kA at 415 V, and 53 kA at 690 V — figures that cover most industrial fault-current scenarios without needing a current-limiting upstream device. The ETU350 electronic trip unit gives adjustable long-time pickup (Ir) from 0.5 to 1.0 × Iu, short-time delay (tsd) from 0.04 to 0.4 s, and instantaneous pickup (Ii) up to 10 000 A. That range suits feeder protection where coordination with downstream breakers matters. Dimensions are 210 mm wide, 320 mm high, 120 mm deep. Front protection is IP40.","metaTitle":"Siemens 3VA2510-5HN32-0AD0 SENTRON MCCB, 1000 A, 187 kA","metaDescription":"Siemens 3VA2510-5HN32-0AD0 SENTRON molded case circuit breaker, 3-pole, 1000 A rated, 187 kA at 240 V. ETU350 release. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"120 mm","Width":"210 mm","Height":"320 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 690 V":"53 kA","at 40 °C":"1 000 A","at 45 °C":"1 000 A","at 50 °C":"1 000 A","at 55 °C":"1 000 A","at 60 °C":"955 A","at 65 °C":"885 A","at 70 °C":"815 A","Width [in]":"8.3 in","Height [in]":"12.6 in","Number of poles":"3","Product version":"Line protection","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"10 000","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"123 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"1 000 A","Rated insulation voltage Ui":"800 V","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.04 s","Adjustable response value current / Ir max.":"1 000 A","Adjustable response value current / li max.":"10 000 A","Adjustable response value current / li min.":"10 000 A","Adjustable response value current / lr min.":"400 A","Adjustable response value current / Isd max.":"10 000 A","Adjustable response value current / Isd min.":"1 500 A","Neutral conductors / upgradeable/retrofittable":"No","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"1 000 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 4"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=645728&mlfb=3VA2510-5HN32-0AD0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2510-5HN32-0AD0/alternatives.json"},"ai":{"faq":[{"question":"What trip unit does the 3VA2510-5HN32-0AD0 use?","answer":"The ETU350 electronic trip unit with adjustable long-time, short-time, and instantaneous settings."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2510-5HN32-0AD0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2510-5HN32-0AD0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}