{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2510-5HN32-0CC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2510-5HN32-0CC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2510-5HN32-0CC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2510-5HN32-0CC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON series, molded case circuit breaker, 3VA2510-5HN32-0CC0, 3-pole, 1000 A, 187 kA at 240 V, ETU350 release.","salesMarkdown":"## What this MCCB does and the ratings that matter The Siemens SENTRON 3VA2510-5HN32-0CC0 is a 3-pole molded case circuit breaker rated for line protection, carrying a continuous current of 1 000 A at 40 °C and an insulation voltage of 800 V. The ETU350 electronic trip unit gives you adjustable overload and short-circuit protection: Ir from 400 A up to 1 000 A, and Isd (short-time delay) adjustable between 0.04 s and 0.4 s. The breaking capacity is 187 kA at 240 V, 121 kA at 415 V, and 53 kA at 690 V — enough to handle high-fault utility feeds or large transformer secondaries without cascading upstream. At 60 °C ambient the breaker derates to 955 A, at 65 °C to 885 A, and at 70 °C to 815 A — so if your panel runs hot, size the load accordingly. The 3VA2510-5HN32-0CC0 measures 210 mm wide, 320 mm high, and 120 mm deep. The 210 mm width (8.3 in) determines the mounting footprint; plan for a 3-pole breaker cutout. ## What the ETU350 release gives you Long-time pickup Ir is adjustable from 0.4 to 1.0 × In (400–1 000 A), with time delay tr from 0.5 s to 17 s at 6× Ir. Short-time pickup Isd is adjustable from 1.5 to 10 × Ir (1 500–10 000 A), with delay tsd from 0.04 s to 0.4 s. Instantaneous pickup Ii is fixed at 10 000 A. This selectivity range lets you coordinate with downstream breakers without nuisance tripping on motor inrush.","metaTitle":"Siemens SENTRON 3VA2510-5HN32-0CC0 MCCB, 1000 A, 187 kA at 2","metaDescription":"Siemens SENTRON 3VA2510-5HN32-0CC0 molded case circuit breaker, 3-pole, 1000 A rated current, 187 kA breaking capacity at 240 V. ETU350 release. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"120 mm","Width":"210 mm","Height":"320 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 690 V":"53 kA","at 40 °C":"1 000 A","at 45 °C":"1 000 A","at 50 °C":"1 000 A","at 55 °C":"1 000 A","at 60 °C":"955 A","at 65 °C":"885 A","at 70 °C":"815 A","Width [in]":"8.3 in","Height [in]":"12.6 in","Number of poles":"3","Product version":"Line protection","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"10 000","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"123 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"1 000 A","Rated insulation voltage Ui":"800 V","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.04 s","Adjustable response value current / Ir max.":"1 000 A","Adjustable response value current / li max.":"10 000 A","Adjustable response value current / li min.":"10 000 A","Adjustable response value current / lr min.":"400 A","Adjustable response value current / Isd max.":"10 000 A","Adjustable response value current / Isd min.":"1 500 A","Neutral conductors / upgradeable/retrofittable":"No","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"1 000 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 4"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=645739&mlfb=3VA2510-5HN32-0CC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2510-5HN32-0CC0/alternatives.json"},"ai":{"faq":[{"question":"Who supplies 3VA2510-5HN32-0CC0 and how is it quoted for volume purchases?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is 3VA2510-5HN32-0CC0's listed depth?","answer":"The listed depth is 120 mm, which fits standard 200 mm deep enclosures with room for wiring gutters."},{"question":"What is 3VA2510-5HN32-0CC0's listed width?","answer":"The listed width is 210 mm (8.3 in), determining the mounting cutout for this 3-pole breaker."},{"question":"What compliance documentation does this brand provide for 3VA2510-5HN32-0CC0?","answer":"The SENTRON brand typically provides RoHS, REACH, UL, and IEC compliance documentation. Specific declarations are available upon request with the order."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2510-5HN32-0CC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2510-5HN32-0CC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}