{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2510-5HN32-0DL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2510-5HN32-0DL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2510-5HN32-0DL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2510-5HN32-0DL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2510-5HN32-0DL0, molded case circuit breaker, 3-pole, 1000 A rated continuous current, ETU350 electronic trip unit, 187 kA interrupting at 240 V, 121 kA at 415 V, 53 kA at 690 V.","salesMarkdown":"## Thermal derating — the real-world number At 60 °C it derates to 955 A, at 65 °C to 885 A, and at 70 °C to 815 A. ## Trip unit and adjustable settings The ETU350 release gives you adjustable long-time pickup Ir from 0.5 to 1.0 x Iu (500 to 1000 A), short-time delay tsd from 0.04 to 0.4 s, and instantaneous pickup Ii adjustable up to 10 000 A. That range lets you coordinate downstream feeders while keeping the main breaker selective — useful on a distribution board where you don't want a branch fault taking the whole panel dark. The 3VA2510-5HN32-0DL0 measures 120 mm deep by 210 mm wide by 320 mm tall — that's about 8.3 x 12.6 inches in the old measure. Front protection is IP40, meaning it's sealed against tools and wires but not against washdown; keep it inside the enclosure, not on the door.","metaTitle":"Siemens 3VA2510-5HN32-0DL0 SENTRON MCCB, 1000 A, 187 kA at 2","metaDescription":"Siemens 3VA2510-5HN32-0DL0 SENTRON molded case circuit breaker, 1000 A rated, 187 kA interrupting at 240 V. ETU350 release. Current production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"120 mm","Width":"210 mm","Height":"320 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 690 V":"53 kA","at 40 °C":"1 000 A","at 45 °C":"1 000 A","at 50 °C":"1 000 A","at 55 °C":"1 000 A","at 60 °C":"955 A","at 65 °C":"885 A","at 70 °C":"815 A","Width [in]":"8.3 in","Height [in]":"12.6 in","Number of poles":"3","Product version":"Line protection","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"10 000","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"123 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"1 000 A","Rated insulation voltage Ui":"800 V","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.04 s","Adjustable response value current / Ir max.":"1 000 A","Adjustable response value current / li max.":"10 000 A","Adjustable response value current / li min.":"10 000 A","Adjustable response value current / lr min.":"400 A","Adjustable response value current / Isd max.":"10 000 A","Adjustable response value current / Isd min.":"1 500 A","Neutral conductors / upgradeable/retrofittable":"No","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"1 000 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 4"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=645745&mlfb=3VA2510-5HN32-0DL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2510-5HN32-0DL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2510-5HN32-0DL0 and how do I get a price?","answer":"This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time."},{"question":"What trip unit does 3VA2510-5HN32-0DL0 use?","answer":"It uses the ETU350 electronic trip unit with adjustable long-time, short-time, and instantaneous settings."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2510-5HN32-0DL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2510-5HN32-0DL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}