{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2510-6HK32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2510-6HK32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2510-6HK32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2510-6HK32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON, molded case circuit breaker, 3VA2510-6HK32-0AA0, 3-pole, 1000 A rated continuous current, 242 kA interrupting at 240 V, ETU340 electronic trip unit, line protection.","salesMarkdown":"The Siemens SENTRON 3VA2510-6HK32-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current Iu of 1000 A at 40 °C ambient and an insulation voltage Ui of 800 V. ## Thermal derating and trip unit Full 1000 A rating holds through 55 °C; at 60 °C it derates to 955 A, at 65 °C to 885 A, and at 70 °C to 815 A. The ETU340 electronic overcurrent release is adjustable for Ir and tr — Ir maxes at 1000 A with a fixed tr of 1300 ms, meaning the long-time pickup and delay are set for coordination with downstream devices. Power loss maxes at 330 W, so panel ventilation matters at full load. Dimensions: 320 mm high, 210 mm wide, 120 mm deep — fits standard MCCB panel cutouts. Front protection is IP40, suitable for enclosed switchboards; storage range -40 °C to 80 °C, operating -25 °C to 70 °C.","metaTitle":"Siemens SENTRON 3VA2510-6HK32-0AA0 MCCB, 1000 A, 242 kA at 2","metaDescription":"Siemens SENTRON 3VA2510-6HK32-0AA0 molded case circuit breaker, 3-pole, 1000 A rated, 242 kA at 240 V, ETU340 release, line protection. Current lifecycle. Sourced to order against","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"120 mm","Width":"210 mm","title":"3VA2510-6HK32-0AA0","Height":"320 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"74 kA","at 40 °C":"1 000 A","at 45 °C":"1 000 A","at 50 °C":"1 000 A","at 55 °C":"1 000 A","at 60 °C":"955 A","at 65 °C":"885 A","at 70 °C":"815 A","Depth [in]":"4.7 in","Width [in]":"8.3 in","Height [in]":"12.6 in","description":"circuit breaker 3VA2 IEC frame 1000 breaking capacity class H Icu=85kA @ 415V 3-pole, line protection ETU340, ELISA LI, In=1000A overload protection Ir=400A...1000A short-circuit protection Ii=10 x In nut keeper kit","Number of poles":"3","Product version":"Line protection","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"10 000","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"330 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"1 000 A","Rated insulation voltage Ui":"800 V","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU340","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1300","Adjustable response value time / tr min.":"1300","Adjustable response value current / Ir max.":"1 000 A","Adjustable response value current / li max.":"10 000 A","Adjustable response value current / li min.":"10 000 A","Adjustable response value current / lr min.":"400 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"ELISA LI","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"1 000 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 4"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/67b9c867aa0e85cb330ebd808a6d2b9d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=645795&mlfb=3VA2510-6HK32-0AA0"},"ai":{"faq":[{"question":"Where can I buy 3VA2510-6HK32-0AA0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time."},{"question":"What is 3VA2510-6HK32-0AA0's interrupting capacity at 240 V?","answer":"242 kA at 240 V, with 187 kA at 415 V and 440 V, 121 kA at 500 V, and 74 kA at 690 V."},{"question":"What is the rated continuous current of 3VA2510-6HK32-0AA0?","answer":"1000 A at 40 °C through 55 °C, derating to 955 A at 60 °C, 885 A at 65 °C, and 815 A at 70 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2510-6HK32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2510-6HK32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}