{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2510-6HM32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2510-6HM32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2510-6HM32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2510-6HM32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2, molded case circuit breaker, 3-pole, 1000 A, 242 kA at 240 V, ETU330 electronic trip unit, line protection version.","salesMarkdown":"The Siemens 3VA2510-6HM32-0AA0 is a SENTRON 3VA2 molded case circuit breaker (MCCB) in the line protection version, rated for 1000 A continuous current at 40 °C with a 3-pole configuration. At 60 °C it drops to 955 A, at 70 °C to 815 A. That thermal curve matters when the breaker shares a crowded panel with other heat sources; the 330 W maximum power loss is the heat you need to vent. The ETU330 electronic trip unit gives adjustable long-time pickup (Ir) from 0.5 to 1.0 × Iu and adjustable long-time delay (tr) from 0.5 to 17 seconds. That lets you coordinate selectively with downstream breakers — critical for keeping a fault from taking out the whole bus. Front protection is IP40, so it's suited for enclosed distribution boards where tools and fingers stay out. No communication function onboard; this is a straight line-protection breaker with no integrated metering or Modbus.","metaTitle":"Siemens 3VA2510-6HM32-0AA0 SENTRON MCCB, 1000 A, 242 kA at 2","metaDescription":"Siemens 3VA2510-6HM32-0AA0 SENTRON molded case circuit breaker, 3-pole, 1000 A rated continuous current, 242 kA interrupting at 240 V. ETU330 release. Active production. Sourced to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"120 mm","Width":"210 mm","title":"3VA2510-6HM32-0AA0","Height":"320 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"74 kA","at 40 °C":"1 000 A","at 45 °C":"1 000 A","at 50 °C":"1 000 A","at 55 °C":"1 000 A","at 60 °C":"955 A","at 65 °C":"885 A","at 70 °C":"815 A","Depth [in]":"4.7 in","Width [in]":"8.3 in","Height [in]":"12.6 in","description":"circuit breaker 3VA2 IEC frame 1000 breaking capacity class H Icu=85kA @ 415V 3-pole, line protection ETU330, LIG, In=1000A overload protection Ir=400A...1000A short-circuit protection Ii=1.5...10 x In ground-fault protection Ig=0.2...1 x In, tg=0.1/0.3s nut keeper kit","Number of poles":"3","Product version":"Line protection","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"330 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"1 000 A","Rated insulation voltage Ui":"800 V","Ground fault monitoring version":"Summation current formation L-conductor","Design of the overcurrent release":"ETU330","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value current / Ir max.":"1 000 A","Adjustable response value current / lg max.":"1 000 A","Adjustable response value current / lg min.":"200 A","Adjustable response value current / li max.":"10 000 A","Adjustable response value current / li min.":"1 500 A","Adjustable response value current / lr min.":"400 A","Adjustable response value current / tg max.":"0.3 s","Adjustable response value current / tg min.":"0.1 s","Ground fault protection can be switched ON/OFF":"No","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LIG","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"1 000 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Mechanical service life (switching cycles) / typical":"10 000","Type of electrical connection / for main current circuit":"on both sides nut keeper kit","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 4 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/13eb8ffcdcf71aad9e482a500dccd9ee.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=645799&mlfb=3VA2510-6HM32-0AA0"},"ai":{"faq":[{"question":"Does the 3VA2510-6HM32-0AA0 have communication capability?","answer":"No. The communication function is listed as 'No' — this is a standalone line-protection breaker with no onboard metering, Modbus, or network interface."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2510-6HM32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2510-6HM32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}