{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2510-6HN32-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2510-6HN32-0AB0","canonicalUrl":"https://aoctrl.com/siemens/3VA2510-6HN32-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2510-6HN32-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2510-6HN32-0AB0, molded case circuit breaker, 3-pole, 1000 A rated continuous current, ETU350 electronic trip unit, line protection version.","salesMarkdown":"That 1 000 A holds flat from 40 °C through 55 °C ambient — no derating needed in a typical warm panel — then steps down to 955 A at 60 °C, 885 A at 65 °C, and 815 A at 70 °C. For a 1 000 A bus or feeder, the thermal curve means you can run it at full rating in most enclosures without oversizing the cabinet ventilation. The interrupting ratings are the headline: 242 kA at 240 V, 187 kA at 415 V, and still 74 kA at 690 V. The ETU350 electronic trip unit gives adjustable long-time pickup (Ir) from 0.5 to 1 000 A, short-time delay (tsd) from 0.04 to 0.4 s, and instantaneous pickup (Ii) up to 10 000 A, so you can coordinate selectively downstream without sacrificing speed on hard faults. The breaker measures 210 mm wide, 320 mm high, and 120 mm deep — a standard MCCB footprint for the 1 000 A frame class. Depth of 120 mm leaves room behind the panel door for wiring and the ETU interface without forcing a deeper enclosure than the rest of the gear requires. The SENTRON 3VA series carries UL, CSA, and IEC certifications for global acceptance.","metaTitle":"Siemens 3VA2510-6HN32-0AB0 SENTRON MCCB, 1000 A, 3-Pole, ETU","metaDescription":"Siemens SENTRON 3VA2510-6HN32-0AB0 molded case circuit breaker, 1000 A rated, 3-pole, ETU350 release. 242 kA at 240 V, 187 kA at 415 V. Active production, available to order. Reque","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"120 mm","Width":"210 mm","Height":"320 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 690 V":"74 kA","at 40 °C":"1 000 A","at 45 °C":"1 000 A","at 50 °C":"1 000 A","at 55 °C":"1 000 A","at 60 °C":"955 A","at 65 °C":"885 A","at 70 °C":"815 A","Width [in]":"8.3 in","Height [in]":"12.6 in","Number of poles":"3","Product version":"Line protection","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"10 000","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"123 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"1 000 A","Rated insulation voltage Ui":"800 V","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.04 s","Adjustable response value current / Ir max.":"1 000 A","Adjustable response value current / li max.":"10 000 A","Adjustable response value current / li min.":"10 000 A","Adjustable response value current / lr min.":"400 A","Adjustable response value current / Isd max.":"10 000 A","Adjustable response value current / Isd min.":"1 500 A","Neutral conductors / upgradeable/retrofittable":"No","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"1 000 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 4"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=645802&mlfb=3VA2510-6HN32-0AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2510-6HN32-0AB0/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of 3VA2510-6HN32-0AB0?","answer":"120 mm. That is the body depth behind the panel face, not including handle or accessory protrusion."},{"question":"What is the width of 3VA2510-6HN32-0AB0?","answer":"210 mm (8.3 in). This is the critical dimension for multi-unit spacing on a mounting plate or DIN-rail assembly."},{"question":"Will 3VA2510-6HN32-0AB0 drop into a panel specified around 5SQ2370-2YA05 without rewiring?","answer":"Not without verification. The 5SQ2370-2YA05 series may share the SENTRON 3VA frame, but the ETU350 release, interrupting ratings, and accessory positions differ. Compare the mounting hole pattern, bus-bar spacing, and terminal layout from the respective datasheets before assuming a drop-in fit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2510-6HN32-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2510-6HN32-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}