{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2510-6HN32-0AF0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2510-6HN32-0AF0","canonicalUrl":"https://aoctrl.com/siemens/3VA2510-6HN32-0AF0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2510-6HN32-0AF0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2510-6HN32-0AF0, molded case circuit breaker, 3-pole, 1000 A, ETU350 electronic trip unit, line protection, 242 kA at 240 V, 187 kA at 415 V, 74 kA at 690 V.","salesMarkdown":"The interrupting capacity at 240 V is 242 kA, at 415 V it is 187 kA, and at 690 V it is 74 kA — figures that govern the available fault current the breaker can safely clear without upstream coordination failure. The ETU350 electronic trip unit provides adjustable long-time (tr) from 0.5 to 17 seconds and short-time delay (tsd) from 0.04 to 0.4 seconds, plus an instantaneous pickup (li) adjustable up to 10 000 A. That means the breaker can be tuned for selectivity with downstream devices, a key requirement for a main or feeder breaker in a distribution panel. Thermal derating is flat at 1 000 A from 40 °C through 55 °C, then drops to 955 A at 60 °C, 885 A at 65 °C, and 815 A at 70 °C. The breaker measures 210 mm wide, 320 mm high, and 120 mm deep. The width of 210 mm (8.3 in) means it occupies three pole spaces in a typical panelboard or MCC bucket. No communication function is built in; the ETU350 is a standalone electronic trip unit without Modbus or PROFIBUS — coordination settings are adjusted locally via the trip unit dials.","metaTitle":"Siemens 3VA2510-6HN32-0AF0 SENTRON MCCB, 1000 A, 3-Pole, ETU","metaDescription":"Siemens 3VA2510-6HN32-0AF0 SENTRON molded case circuit breaker, 1000 A rated current, 3-pole, ETU350 release, 242 kA at 240 V. Current lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"120 mm","Width":"210 mm","Height":"320 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 690 V":"74 kA","at 40 °C":"1 000 A","at 45 °C":"1 000 A","at 50 °C":"1 000 A","at 55 °C":"1 000 A","at 60 °C":"955 A","at 65 °C":"885 A","at 70 °C":"815 A","Width [in]":"8.3 in","Height [in]":"12.6 in","Number of poles":"3","Product version":"Line protection","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"10 000","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"123 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"1 000 A","Rated insulation voltage Ui":"800 V","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.04 s","Adjustable response value current / Ir max.":"1 000 A","Adjustable response value current / li max.":"10 000 A","Adjustable response value current / li min.":"10 000 A","Adjustable response value current / lr min.":"400 A","Adjustable response value current / Isd max.":"10 000 A","Adjustable response value current / Isd min.":"1 500 A","Neutral conductors / upgradeable/retrofittable":"No","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"1 000 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 4"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=645806&mlfb=3VA2510-6HN32-0AF0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2510-6HN32-0AF0/alternatives.json"},"ai":{"faq":[{"question":"What trip unit does 3VA2510-6HN32-0AF0 use?","answer":"It uses the ETU350 electronic trip unit with adjustable long-time, short-time, and instantaneous settings."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2510-6HN32-0AF0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2510-6HN32-0AF0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}