{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2510-6HN32-0CC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2510-6HN32-0CC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2510-6HN32-0CC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2510-6HN32-0CC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2510-6HN32-0CC0, molded case circuit breaker, 3-pole, 1000 A, ETU350 electronic trip unit, line protection version, 242 kA at 240 V.","salesMarkdown":"## SENTRON 3VA2510-6HN32-0CC0 — 1000 A MCCB with ETU350 Release The ETU350 electronic trip unit provides adjustable long-time (tr: 0.5–17 s), short-time (tsd: 0.04–0.4 s), and instantaneous (Ii up to 10 000 A) response values, giving the selectivity engineer fine-grained coordination control for downstream feeders. Breaking capacity reaches 242 kA at 240 V, 187 kA at 415 V, and 74 kA at 690 V — figures that place it in a high-interrupting class for industrial main or tie-breaker positions where fault currents are substantial. ## Thermal Management and Panel Fit Rated continuous current holds at 1000 A from 40 °C through 55 °C ambient; derating begins at 60 °C (955 A), dropping to 815 A at 70 °C. Maximum power loss is 123 W — a figure that drives ventilation planning in the enclosure, particularly when multiple breakers share a compartment. Dimensions are 210 mm wide × 320 mm high × 120 mm deep (8.3 × 12.6 × 4.7 in), a 3-pole footprint that fits standard SENTRON mounting bases. Front protection is IP40; the enclosure cutout and busbar connections must respect the live-part clearance this rating implies.","metaTitle":"Siemens 3VA2510-6HN32-0CC0 SENTRON MCCB, 1000 A, 3-Pole, ETU","metaDescription":"Siemens 3VA2510-6HN32-0CC0 SENTRON molded case circuit breaker, 1000 A rated continuous current, 3-pole, ETU350 release, 242 kA at 240 V. Current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"120 mm","Width":"210 mm","Height":"320 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 690 V":"74 kA","at 40 °C":"1 000 A","at 45 °C":"1 000 A","at 50 °C":"1 000 A","at 55 °C":"1 000 A","at 60 °C":"955 A","at 65 °C":"885 A","at 70 °C":"815 A","Width [in]":"8.3 in","Height [in]":"12.6 in","Number of poles":"3","Product version":"Line protection","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"10 000","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"123 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"1 000 A","Rated insulation voltage Ui":"800 V","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.04 s","Adjustable response value current / Ir max.":"1 000 A","Adjustable response value current / li max.":"10 000 A","Adjustable response value current / li min.":"10 000 A","Adjustable response value current / lr min.":"400 A","Adjustable response value current / Isd max.":"10 000 A","Adjustable response value current / Isd min.":"1 500 A","Neutral conductors / upgradeable/retrofittable":"No","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"1 000 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 4"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=645425&mlfb=3VA2510-6HN32-0CC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2510-6HN32-0CC0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2510-6HN32-0CC0 at 415 V?","answer":"At 415 V the breaking capacity is 187 kA; at 240 V it reaches 242 kA, and at 690 V it is rated 74 kA."},{"question":"What are the adjustable trip settings on the ETU350 release?","answer":"The ETU350 allows adjustable long-time current Ir from 400 A to 1000 A, long-time delay tr from 0.5 to 17 s, short-time delay tsd from 0.04 to 0.4 s, and instantaneous pickup Ii up to 10 000 A."},{"question":"How do I get current pricing and availability for 3VA2510-6HN32-0CC0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for current pricing and confirmed availability — figures are provided at quote time, not on a public listing."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2510-6HN32-0CC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2510-6HN32-0CC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}