{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2510-6HN32-0JL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2510-6HN32-0JL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2510-6HN32-0JL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2510-6HN32-0JL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON series, Molded case circuit breaker, 3VA2510-6HN32-0JL0, 3-pole, 1000 A rated continuous current, ETU350 electronic trip unit, 242 kA interrupting at 240 V.","salesMarkdown":"## What this 1000 A MCCB does for a line-down call It's built for line protection — main feeder or large downstream distribution — not motor protection. The interrupting ratings are serious: 242 kA at 240 V, 187 kA at 415 V, 74 kA at 690 V. That SCCR headroom means it can live upstream of a fault without cascading, which is exactly what you want when the main breaker is the only thing between a bolted fault and a whole panel replacement. Thermal derating stays flat at 1000 A all the way to 55 °C. At 60 °C it drops to 955 A, at 70 °C to 815 A. The ETU350 release gives you adjustable Ir from 0.5 to 1.0 × In, plus adjustable short-time (tsd 0.04–0.4 s) and instantaneous (li up to 10 000 A). That's enough flexibility to coordinate with downstream breakers without a separate relay. ## Panel fit — 320 × 210 × 120 mm Footprint: 320 mm tall, 210 mm wide, 120 mm deep. That 210 mm width is a standard 8.3-inch form factor for this amp class. The IP40 front protection means it's splash-safe on the face but not sealed for washdown — this is a panel-mount breaker, not a standalone enclosure.","metaTitle":"Siemens SENTRON 3VA2510-6HN32-0JL0 MCCB, 1000 A, 3-Pole","metaDescription":"Siemens SENTRON 3VA2510-6HN32-0JL0 molded case circuit breaker. 1000 A rated, 3-pole, ETU350 release. 242 kA at 240 V. Current production. Sourced to order. RFQ for pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"120 mm","Width":"210 mm","Height":"320 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 690 V":"74 kA","at 40 °C":"1 000 A","at 45 °C":"1 000 A","at 50 °C":"1 000 A","at 55 °C":"1 000 A","at 60 °C":"955 A","at 65 °C":"885 A","at 70 °C":"815 A","Width [in]":"8.3 in","Height [in]":"12.6 in","Number of poles":"3","Product version":"Line protection","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"10 000","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"123 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"1 000 A","Rated insulation voltage Ui":"800 V","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.04 s","Adjustable response value current / Ir max.":"1 000 A","Adjustable response value current / li max.":"10 000 A","Adjustable response value current / li min.":"10 000 A","Adjustable response value current / lr min.":"400 A","Adjustable response value current / Isd max.":"10 000 A","Adjustable response value current / Isd min.":"1 500 A","Neutral conductors / upgradeable/retrofittable":"No","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"1 000 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 4"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=645439&mlfb=3VA2510-6HN32-0JL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2510-6HN32-0JL0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2510-6HN32-0JL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2510-6HN32-0JL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}