{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2510-6HN32-0KA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2510-6HN32-0KA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2510-6HN32-0KA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2510-6HN32-0KA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2510-6HN32-0KA0, molded case circuit breaker, 3-pole, line protection, 1000 A rated continuous current, ETU350 electronic trip unit, interrupting capacity 242 kA at 240 V, 187 kA at 415 V, 74 kA at 690 V.","salesMarkdown":"Rated continuous current Iu is 1000 A, and at 40 °C the breaker holds that rating flat; derating starts at 60 °C (955 A), dropping to 815 A at 70 °C. That thermal curve is the one to check if this lands in a hot enclosure or next to other high-current devices. Interrupting capacity is the headline number for a main breaker: 242 kA at 240 V, 187 kA at 415 V, and 74 kA at 690 V. Those figures cover most industrial service-entrance and high-fault panelboard applications, including installations where the available fault current exceeds 100 kA at the lower voltages. The ETU350 electronic trip unit gives adjustable long-time pickup (Ir) from 0.5 to 1.0 × Iu — so 500 A to 1000 A — and short-time delay (tsd) adjustable 0.04 to 0.4 seconds. That selectivity window is what a site electrical engineer uses to coordinate downstream breakers and keep a fault from taking out the whole bus. Dimensions are 210 mm wide, 320 mm tall, 120 mm deep — a 3-pole frame that fits standard SENTRON mounting patterns. The 120 mm depth is the front-to-back projection behind the panel door; verify clearance against the backplane or busbar stack, especially if a rear-connection kit is used. No washdown rating; keep this inside a cabinet. The ETU350 trip unit supports adjustable long-time, short-time, and instantaneous settings (li adjustable up to 10 000 A). No ground-fault monitoring version is fitted on this variant.","metaTitle":"Siemens 3VA2510-6HN32-0KA0 SENTRON MCCB, 1000 A, 3-Pole, ETU","metaDescription":"Siemens 3VA2510-6HN32-0KA0 SENTRON molded case circuit breaker, 1000 A rated continuous current, 3-pole, ETU350 electronic trip unit, 242 kA at 240 V. Current production. Available","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"120 mm","Width":"210 mm","Height":"320 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 690 V":"74 kA","at 40 °C":"1 000 A","at 45 °C":"1 000 A","at 50 °C":"1 000 A","at 55 °C":"1 000 A","at 60 °C":"955 A","at 65 °C":"885 A","at 70 °C":"815 A","Width [in]":"8.3 in","Height [in]":"12.6 in","Number of poles":"3","Product version":"Line protection","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"10 000","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"123 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"1 000 A","Rated insulation voltage Ui":"800 V","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.04 s","Adjustable response value current / Ir max.":"1 000 A","Adjustable response value current / li max.":"10 000 A","Adjustable response value current / li min.":"10 000 A","Adjustable response value current / lr min.":"400 A","Adjustable response value current / Isd max.":"10 000 A","Adjustable response value current / Isd min.":"1 500 A","Neutral conductors / upgradeable/retrofittable":"No","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"1 000 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 4"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=645440&mlfb=3VA2510-6HN32-0KA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2510-6HN32-0KA0/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of this MCCB?","answer":"The depth is 120 mm. That is the front-to-back dimension behind the panel door."},{"question":"What is the width of this MCCB?","answer":"The width is 210 mm, which is 8.3 inches."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2510-6HN32-0KA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2510-6HN32-0KA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}