{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2510-6JP32-0HH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2510-6JP32-0HH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2510-6JP32-0HH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2510-6JP32-0HH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA2 IEC frame 1000 MCCB, 3-pole, breaking capacity class H, Icu=85kA @ 415V, ETU550 LSI trip unit, In=1000A, shunt trip left 24V AC/DC.","salesMarkdown":"The Siemens 3VA2510-6JP32-0HH0 is a 3-pole IEC molded-case circuit breaker from the 3VA2 series, built on a 1000 A frame with a class H breaking capacity — meaning it interrupts 85 kA at 415 V without damage. That puts it in the high-interrupting tier for industrial main feeders and large sub-distribution boards where fault current runs hot. The ETU550 electronic trip unit gives you LSI protection: long-time (Ir) adjustable 400–1000 A, short-time (Isd) 0.6–10x In, and instantaneous (Ii) 1.5–10x In. That range covers everything from a 400 A tap to a full 1000 A bus, with selectivity headroom for downstream breakers. For the service-entrance or main-tie role, that number decides whether the gear upstream survives a bolted fault. The ETU550 is an LSI-only unit (no ground-fault element), so if you need GF protection you add an external core-balance CT and a separate relay. The shunt trip on the left side, 24 V AC/DC, lets a remote E-stop or fire-alarm system drop the main breaker without anyone pulling the handle. Two auxiliary switches (changeover H) and one trip-alarm switch are factory-fitted — that gives the PLC a status contact for open/closed and a separate one for trip events.","metaTitle":"Siemens 3VA2510-6JP32-0HH0 3VA2 IEC Breaker, 85kA @ 415V","metaDescription":"Siemens 3VA2510-6JP32-0HH0 circuit breaker, 3VA2 IEC frame 1000, 85kA Icu @ 415V, ETU550 LSI, 1000A frame. Active lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1527901&mlfb=3VA2510-6JP32-0HH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2510-6JP32-0HH0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this breaker?","answer":"The 3VA2510-6JP32-0HH0 has a class H breaking capacity with Icu = 85 kA at 415 V AC, suitable for high-fault-current industrial mains."},{"question":"What trip unit does the 3VA2510-6JP32-0HH0 use?","answer":"It uses the ETU550 electronic trip unit with LSI protection: long-time Ir adjustable 400–1000 A, short-time Isd 0.6–10x In, and instantaneous Ii 1.5–10x In."},{"question":"Where can I buy 3VA2510-6JP32-0HH0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2510-6JP32-0HH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2510-6JP32-0HH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}